F622138
May 14, 2026

F622138

F622138 (Material Number 984622138) is an upgraded replacement version of HIMA F6221: 8-channel SIL3 analog input (4–20mA/0–10V), TMR triple redundancy, directly interchangeable. 1. Core Parameters (984622138) Model: F622138 (984622138) Function: 8-channel AI, software selectable from 4–20mA/0–20mA/0–5V/0–10V Safety Level: SIL3, AK6, Cat.4/PL e (TÜV) Architecture: TMR triple redundancy (hardware voting) Resolution: 16 bits Input Impedance: Current ≈ 50Ω; Voltage ≈ 100kΩ Isolation: Channel - Backplane 200V AC; Channel-to-channel isolation Accuracy: ±0.1% FS at 25℃; ±0.3% FS at 0–+60℃ Refresh / Response: 50ms; Safety Response < 450ms Filtering: Hardware low-pass, τ ≈ 10ms Power Supply: 5V DC ≈ 80mA; 24V DC≈50mA Temperature: -20℃ ~ +60℃ Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg Installation: DIN rail, supports hot swapping Diagnosis: Open circuit / Short circuit / Overrange / Drift detection

Description

F622138 (Material Number 984622138) is an upgraded replacement version of HIMA F6221: 8-channel SIL3 analog input (4–20mA/0–10V), TMR triple redundancy, directly interchangeable.

1. Core Parameters (984622138)

Model: F622138 (984622138)

Function: 8-channel AI, software selectable from 4–20mA/0–20mA/0–5V/0–10V

Safety Level: SIL3, AK6, Cat.4/PL e (TÜV)

Architecture: TMR triple redundancy (hardware voting)

Resolution: 16 bits

Input Impedance: Current ≈ 50Ω; Voltage ≈ 100kΩ

Isolation: Channel - Backplane 200V AC; Channel-to-channel isolation

Accuracy: ±0.1% FS at 25℃; ±0.3% FS at 0–+60℃

Refresh / Response: 50ms; Safety Response < 450ms

Filtering: Hardware low-pass, τ ≈ 10ms

Power Supply: 5V DC ≈ 80mA; 24V DC≈50mA

Temperature: -20℃ ~ +60℃

Dimensions/Weight: 4TE (25×203×127mm) / Approximately 0.5kg

Installation: DIN rail, supports hot swapping

Diagnosis: Open circuit / Short circuit / Overrange / Drift detection

II. Relationship with the Standard Model F6221 (984622102)

F622138 (984622138): Hardware/Firmware upgrade, enhanced performance/diagnosis, batch update, fully interchangeable

F6221 (984622102): Standard model, identical functions

III. Differences from Similar Models F622138 vs F622038

F622138: Analog quantity (4–20mA/0–10V), connected to pressure / level / flow

F622038: Thermocouple (J/K/T...), with cold junction compensation, specifically for temperature measurement F622138 vs F6217

F6217: 12-bit, basic diagnosis

F622138: 16-bit, high precision, strong diagnosis, interchangeable directly

IV. Main Matters (Installation / Wiring / Maintenance)

1. Installation

Environment: Dust-free, dry, free from corrosion, anti-condensation

Heat dissipation: ≥ 50mm above and below, away from heat sources

Grounding: Cabinet independent ground ≤ 4Ω

Hot swapping: Online replacement after disabling software

2. Wiring (28-pin)

Signal: Shielded twisted pair, single-ended grounding (module side)

Cabling: Separate slot from high voltage ≥ 10cm, avoid long parallel runs

Power supply: 24V DC ±10%, reliable connection to GND

3. Configuration and Calibration

Software: ELOP II selects signal type / range / filtering, takes effect after download

Calibration: Once a year; if error > ±0.2% FS, re-calibrate

4. Maintenance and Faults

Status: Green LED = normal, Red = fault; regularly check diagnostic logs

Troubleshooting: Faulty → Wiring / Shielding / Grounding; Channel failure → Replace channel for testing, if abnormal then replace module