F6216
Description
I. Product Overview
HIMA F6216 is a 4-channel safety-level analog input module (AI), featuring a **triplex redundancy (TMR)** architecture. It is specifically designed for SIL3-level safety control systems (ESD/BMS/HIPPS), compatible with HIMA F3/F4 series safety PLCs, and supports hot swapping and online diagnostics.
II. Core Technical Parameters
1. Basic Parameters
Model: F6216
Number of channels: 4 independent analog input channels
Signal type: 4–20mA (default), 0–10V (software configurable)
Resolution: 12 bits
Safety level: SIL3 (IEC 61508), AK6, Cat.4/PL e (TÜV certification)
Architecture: Triple Redundancy (TMR), 3 CPU hardware voting
Isolation: Electrical isolation between channels and backplane, withstands 200V AC
Input impedance: Current input 100kΩ; Voltage input high impedance
Accuracy: ±0.1% FS (25℃); ±0.3% FS (0–+60℃)
Update cycle: 50ms; Safety response time < 450ms
Filtering: Hardware low-pass filtering, time constant approximately 10ms
2. Environmental and Physical
Operating temperature: -20℃ ~ +60℃
Storage temperature: -40℃ ~ +85℃
Humidity: 5%~95% RH (no condensation)
Size: 4TE (25×203×127mm)
Weight: Approximately 0.5kg
Protection level: IP20
Installation: Standard DIN rail, supports hot swapping
3. Electrical Parameters
Power supply: Backplane 5V DC (powered by CPU)
Power consumption: Approximately 80mA (5V DC)
Connection: Front terminal block, supports 2-wire/3-wire sensors
Diagnosis: Open circuit, short circuit, overrange, power failure detection Table
Terminal Number Signal Explanation
1 CH1+ Positive input of channel 1 (4–20mA/0–10V)
2 CH1- Positive input of channel 1 / Ground
3 CH2+ Positive input of channel 2
4 CH2- Negative input of channel 2 / Ground
5 CH3+ Positive input of channel 3
6 CH3- Negative input of channel 3 / Ground
7 CH4+ Positive input of channel 4
8 CH4- Negative input of channel 4 / Ground
9 GND Reference Ground
10 NC Open Terminal
Four. Functional Characteristics
High reliability of TMR: Three independent channels for sampling and calculation. A single channel failure does not affect the safe operation of the system. It has strong fault tolerance.
Safety Diagnosis: Each channel monitors signal abnormalities in real time. When a fault occurs, it triggers system alarms and records logs. It supports online fault location.
Signal Compatibility: Default 4–20mA (industrial standard). It can be configured as 0–10V through HIMA programming software (such as HIQuad X), suitable for pressure, temperature, level, etc. sensors.
Seamless Integration: Plug and play, compatible with F3311, F3313, F4316 and other CPUs. The backplane bus automatically identifies the module and assigns an address.
Hot Swap: Supports online module replacement without stopping the machine. Maintenance is convenient.
Five. Installation and Wiring Tips
Installation: Insert the module into the 4TE slot of the rack, tighten the fixing screws; ensure it is in the same rack as the CPU module, and the backplane connection is reliable.
Wiring:
Current signal (4–20mA): Connect the positive pole of the sensor to CHx+, and the negative pole to CHx-. No additional resistors are required.
Voltage signal (0–10V): Connect the positive pole of the sensor to CHx+, and the negative pole to CHx-. Ensure that the signal ground is common with the module ground.
Shielded Wire: Single-ended grounding (module side), to avoid circulating interference.
Configuration: Set the channel type, range, filtering parameters, and alarm threshold through the HIQuad X software, and download the configuration to take effect on the CPU.
Six. Fault Troubleshooting
Module no response: Check the 5V power supply on the backplane, whether the module is tightened, and whether the CPU recognizes the module (software diagnosis).
Signal abnormality: Check if the wiring is loose, if the sensor is faulty, if the channel configuration is correct, and if there is electromagnetic interference.
Diagnostic Alarm: View the fault code through the software to locate the faulty channel and type (open circuit / short circuit / overrange).
Seven. Official Information
Manufacturer: German HIMA Paul Hildebrandt GmbH
Certifications: TÜV SIL3, CE, RoHS
Application Scenarios: ESD, BMS, F&G systems in the oil and gas, chemical, power, etc. industries

Get a Quote