F60MI2401
Description
HIMA F60MI2401 (Mixed I/O Module, F60 System)
Positioning: The safety-level mixed I/O module (Digital + Analog) of HIMA HIMatrix F60 system (Digital + Analog), abbreviated as MI2401, is used for digital/analog signal acquisition and control in safety instrument systems (SIS), with SIL3 certification.
I. Model Analysis
F60: Series (HIMatrix F60 rack-mounted SIS)
MI: Mixed Input/Output
24: 24V DC level
01: Hardware version
Alias: F60MI24/01, F60 MI 24 01
II. Core Functions and Channel Configuration
Digital Input DI: 16 channels, 24VDC, source type / drain type selectable, contact point compatibility
Digital Output DO: 8 channels, relay output (24VDC, 0.5A), safety type contacts
Analog Input AI: 8 channels, 4–20mA / 0–10V selectable, 16-bit resolution
Pulse / Counter: 2 channels, maximum 100kHz, 5V/24V level selectable
Safety Isolation: Electrical isolation between I/O and system bus, withstands 1500Vrms
III. Safety Level and Certification
Safety Integrity: SIL3 (IEC 61508), PL e / Cat.4 (EN ISO 13849), AK6
Applicable Standards: IEC 61511 (process industry), EN 50126 (railway SIL4)
Certification Body: TÜV Rheinland
IV. Electrical and Environmental Parameters
Power Supply: 24VDC (18~32V), powered by F60 PS01 power supply
Power Consumption: ≤180mA
Operating Temperature: -20℃ ~ +60℃ (industrial grade)
Protection Grade: IP20 (installed in cabinet)
Size / Weight: Standard F60 rack slot (width 40mm) / approximately 0.4kg
V. Installation and Compatibility
Installation Position: F60 rack slot 3~8 (slot 1 power supply, slot 2 CPU)
System Compatibility: HIMatrix F60 full series (F60CPU01/F60CPU02)
Software Configuration: SILworX (recommended), ELOP II Factory
Hot Swap: Supported, can be replaced online without affecting system operation
VI. Differences from F60DIO24/1601 (Confusing Model)
F60MI2401: Mixed I/O (DI+DO+AI), suitable for analog circuits (such as liquid level, pressure)
F60DIO24/1601: Pure digital I/O (24DI+16DO), no analog input, used for pure switch scenarios (ESD, F&G)
VII. Typical Applications
SIS/ESD: Emergency shutdown system for petrochemicals, natural gas, and power (including analog interlocks)
BMS: Boiler combustion management (flame signal, temperature / pressure analog monitoring)
F&G: Fire and gas detection (gas concentration analog + flame switch quantity)
Compressor Control: Vibration, temperature analog + anti-surge switch quantity interlock