F343034
Description
I. Model Description
Model: F3430 (Standard Model)
F343034: Non-standard model. F3430 is the module body, and the 34 at the end generally represents the version / batch / project suffix. The function is exactly the same as F3430.
Brand: HIMA Black Horse (Germany)
Series: HIMatrix F3 / H41q / H51q Security System
Type: 4-channel fail-safe relay output module
Safety Level: SIL3, PL e, AK6, Cat.4 (TÜV Certified)
Usage: SIS/ESD/BMS/F&G; drives solenoid valves, contactors, alarm lights, small actuators
Installation: Standard 4TE rack, supports hot swapping
II. Electrical Parameters
Channels: 4 independent relays (SPDT single-pole double-throw)
Contact capacity: 250VAC / 30VDC, resistive 5A
Maximum switching voltage: 250VAC / 110VDC
Current per channel: Maximum 500mA (12W), short-circuit protection
Power supply from backplane: 24VDC, power consumption ≤ 120mA
Insulation isolation: System side ↔ Field side 1500Vrms
Operating temperature: -20℃ ~ +60℃
Protection / Size: IP20; 4TE (≈ 20mm wide)
Weight: Approximately 0.15kg
III. Functions and Safety Features
Fault safety: Contacts safely open when power is lost / in case of failure to ensure safe shutdown.
Short-circuit protection: Each output can withstand short circuits without damaging the module.
Self-diagnosis: Full coverage diagnosis for coil / contact faults, short circuits, open circuits.
Status indication: LED per channel, power / fault LED, intuitive maintenance.
Redundancy compatibility: Supports QMR/TMR, meeting high safety redundancy architecture.
IV. Comparison with the Same Series
F3430: 4 channels, small size, low power consumption, 500mA, suitable for solenoid valves / coil-type loads
F3422: 8 channels, standard relays, 5A, universal type
F3423: 8 channels, relay amplification, stronger 24/48V drive, preferred for solenoid valves
V. Wiring and Maintenance
Control input: 24VDC safety signal on system side
Output terminals: Each channel COM / NO / NC
Maintenance: Supports hot swapping without downtime, online replacement
Software: SILworX / ELOP II configuration and fault diagnosis

Get a Quote