F3349
Description
I. Basic Overview
Model: F3349
Brand: HIMA
Black Horse Series: HIMatrix F3 / H41q/H51q
System Module Type: Composite Digital I/O Module (32 DI + 8 DO)
Safety Level: SIL3, AK6, Cat.4/PL e
Applicable Systems: SIS, ESD, BMS, F&G
Configuration Software: SILworX, ELOP II
Installation: Standard rack slots, supports hot swapping
II. Core Electrical Parameters
Channel Configuration: 32 Digital Inputs (DI) + 8 Digital Outputs (DO)
Input Type: 24VDC Source Type / Drain Type (Compatible), High-Level Valid Output Type: 24VDC or 48VDC Active Output (Source Type, L+)
Single Channel Output Current: Maximum 0.5A (Resistive / Inductive), Lamp Load 10W
Output Voltage Drop: ≤ 2V at 500mA Protection Mechanism: Independent Short Circuit, Overcurrent, Surge, ESD Protection
Backplane Power Supply: 5VDC / 0.15A
External Power Supply: 24VDC or 48VDC / 50mA + Load Current
Input Signal: 24VDC, High Level ≥ 15V, Low Level ≤ 5V
Isolation: High Voltage Isolation between Channels and System, Channel-to-Channel
Operating Temperature: -20℃ to +60℃
Storage Temperature: -55℃ to +105℃
Protection Grade: IP20
III. Functions and Diagnostics
Input Function: 32 DI, Supports Relay Contacts / 24V Active Signals, Line Monitoring Output Function: 8 DO, Can Drive 24V/48V Electromagnets, Relays, Contactors
Self-Diagnosis: Full Channel Coverage Self-Diagnosis, Open Circuit / Short Circuit / Overcurrent / Power Supply Abnormal Fault Response: Fault Channel Shutdown, System Alarm, Configurable Safety Status Indicator: Independent RUN/Fault Lights per Channel, Intuitive Status
Line Monitoring Function: Input/Output Loop Open Circuit, Short Circuit Automatic Identification
Safety Features: Compliant with IEC 61508 SIL3, Supports Quadruplex (QMR) Architecture
IV. Typical Applications
ESD Emergency Stop System DI/DO Integrated Interface BMS Boiler Interlock, F&G Fire and Gas System Signal Acquisition and Drive 32 Switching Quantity Signal Input + 8 Actuator Control (Electromagnets / Relays) 24V/48V Mixed Load Control, Saves Rack Space Third-party System Relay Interlock and Signal Interactions
V. Comparison with Similar Series
F3348: 8 DO, 48VDC, 0.5A, Pure Output Module
F3349: 32 DI + 8 DO, 24V/48V Compatible, Composite I/O
F3335: 8 DO, 24VDC, 0.5A, Enhanced Diagnosis
F3332: 8 Relay DO, Passive Relay Contacts, 250VAC/30VDC
VI. Brief Usage Instructions
Module Inserted into Standard Rack Backplane, Automatically Identified, Supports Hot Swap
Input Wiring: 24VDC Sensor / Relay Contact, Common Terminal Connected to 24V Ground
Output Wiring: Positive Terminal of 24V/48V Connected to Output Port, Negative Terminal Connected to Power Ground, Source Type Drive Power: Backplane 5VDC + External 24V/48VDC Simultaneous Power Supply Configuration: Select F3349 from SILworX/ELOP II, Configure DI/DO Logic and Fault Response Maintenance: Online Replacement Does Not Affect Other Modules, Diagnostic Information Available via Software / Hardware Lights