F3333
Description
I. Basic Information
Model: F333 Brand: HIMA (German Rising Star)
Series: HIMatrix F3 / HIMax
Type: 8-channel SIL3 safety digital output (DO, source type, enhanced diagnostics)
Safety level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e, ATEX
Software: SILworX
Applications: ESD/BMS/F&G/SIS, drives solenoid valves, relays, indicator lights (including high-reliability circuits)
II. Hardware Parameters
Power Supply: 24VDC (L+), 5VDC (backplane)
Power Consumption: 5V @ 130mA; 24V @ 180mA (excluding load)
Channels: 8 DO (source type output, enhanced line monitoring)
Output: 24VDC, per channel 0.5A (12W); indicator light ≤ 4W
Load: Resistive / Inductive (≤ 12W), supports high reliability / long-life load
Isolation: Channel-to-channel / Ground safety isolation, enhanced explosion-proof isolation design
Operating Temperature: -25℃~+70℃ (explosion-proof area - 20℃~+50℃)
Size: 4TE (25mm×203mm×127mm)
Weight: Approximately 1.0kg
Hot Swap: Supported
III. Interfaces and Protection
Terminal: 8×DO+, common terminal L-, explosion-proof shielding ground (screw terminal)
Indicator: Per channel LED (operation / fault / line monitoring status)
Protection: Short circuit / overcurrent / overvoltage / reverse polarity, enhanced line monitoring (open circuit / short circuit / load abnormality)
Communication: Backplane bus (connects F3311/F3313/F3318 CPU)
Feature: Full-channel line monitoring + output circuit deep testing, fault location accuracy improvement
IV. Differences from the Core of the Same Series
F3330: 8 channels, 0.5A/channel, source type, basic diagnosis
F3331: 8 channels, 0.5A/channel, open collector, basic diagnosis
F3332: 8 channels, 2A/channel, source type, high-power load
F3333: 8 channels, 0.5A/channel, source type + enhanced diagnosis + high reliability adaptation
V. Key Advantages
Higher diagnostic coverage: Compared to F3330/F3331, add load abnormality, circuit impedance monitoring
High reliability scenarios adaptation: Suitable for frequently operated, long-life requirements of solenoids / relays
Explosion-proof compatibility optimization: Isolation and energy-limiting design adapted to Ex ia/ib explosion-proof areas