F3325
Description
I. Basic Information
Model: F3325
Brand: HIMA Black Horse (Germany)
Series: HIMatrix F3 / HIMax
Type: 6-channel SIL3 safety analog output module (explosion-proof type, Ex)
Application: ESD, BMS, F&G, SIS safety instrumented system, drives explosion-proof field devices (such as F6221 transmitter)
Software: SILworX
Safety Level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e, ATEX explosion-proof certification
Architecture: Single-module safety output, supports TMR system expansion
Status: In production
II. Hardware Parameters
Power Supply: 24VDC, -15% to +20%
Power Consumption: Approximately 15W
Output Channels: 6 analog output channels (AO)
Output Signals: 4-20mA (standard), 0-20mA (optional)
Load Capacity: Maximum 600Ω per channel
Isolation: Channel-to-channel / Ground 2kVrms, explosion-proof isolation design
Operating Temperature: -25℃ to +60℃ (explosion-proof environment -20℃ to +50℃)
Storage Temperature: -40℃ to +85℃
Protection: IP20 (module), compatible with on-site equipment Ex ia/ib
Size: 25mm × 203mm × 127mm
Weight: Approximately 0.8kg
Hot Swap: Supported
III. Interfaces and Protection
Output Terminals: 6 AO + common terminal + explosion-proof shielded ground, screw terminals
Status Indicators: LED per channel (operation / fault / explosion-proof status)
Protection Functions: Short circuit protection, overcurrent protection, overvoltage protection, explosion-proof energy-limiting protection
Communication: Backplane bus (for communication with F3311/F3313/F3318 CPU)
IV. Performance and Safety
Response Time: ≤10ms
Accuracy: ±0.1% FS (25℃), ±0.2% FS (full temperature range)
Self-Diagnosis: Channel-level diagnosis (short circuit, open circuit, overload, explosion-proof abnormality)
Fault Behavior: Single-channel fault does not affect other channels, system alarms and records, explosion-proof fault automatically limits energy
Safety Mechanism: Output circuit redundancy detection, explosion-proof isolation barrier integration, output disconnected to safe state in case of failure
V. Usage Tips (Installation / Wiring / Configuration)
Installation: Insert into the backplane slot of the F3 rack, snap lock; leave 20mm clearance above and below for heat dissipation, away from strong electricity / frequency conversion interference, explosion-proof area should comply with ATEX installation specifications.
Power Supply: 24VDC regulated power supply, positive and negative terminals; FG protective ground and explosion-proof shielded ground are reliably grounded separately to reduce EMC interference and explosion risk.
Output Wiring: 6 AO terminals connect to explosion-proof transmitters (such as F6221) positive terminals, common terminal connects to negative terminals, shield layer is grounded at one end; each channel load ≤ 600Ω, non-explosion-proof equipment must not be connected.
Configuration (SILworX): Add F3325 to the hardware; define channel signal type (4-20mA), range, fault response (hold / safe state), explosion-proof parameters; compile and download to CPU.
Maintenance: Regularly check terminal tightening, LED status, explosion-proof sealing; faults are diagnosed and located through software; support hot swap replacement without shutdown, explosion-proof area maintenance requires power-off and electrical testing.
Compatibility: Can be paired with F3311/F3313/F3318 CPU and F32xx DI module in the same rack; when replacing, update configuration, no need to modify wiring, explosion-proof certification needs to match.

Get a Quote