F332216
Description
I. Basic Information
Model: F3322 (often written as F332216)
Brand: HIMA (Germany)
Series: HIMatrix F3 / HIMax
Type: 16-channel SIL3 safety digital output module
Safety level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e
Software: SILworX
Applications: ESD, BMS, F&G, SIS, drives for solenoid valves, relays, indicator lights, etc.
II. Hardware Parameters
Power Supply: 24VDC, allowing -15% to +20%
Power Consumption: Approximately 12W
Channels: 16 digital outputs (DO)
Output Voltage: 24VDC
Single Channel Current: Maximum 0.5A
Output Type: Drain / Source type, open collector or push-pull selectable
Isolation: Channel-to-channel / Ground 2kVrms
Operating Temperature: -25℃ to +60℃
Storage Temperature: -40℃ to +85℃
Protection: IP20
Size: 25mm × 203mm × 127mm
Weight: Approximately 0.7kg
Hot Swap: Supported
III. Interfaces and Protection
Output: 16 DO channels + common terminal, screw terminals
Indication: LED per channel (operation / fault)
Protection: Short circuit, overcurrent, overvoltage protection per channel
Communication: Backplane bus (for communication with F3311/F3313/F3318 and other CPUs)
IV. Performance and Safety
Response Time: ≤ 5ms
Self-Diagnosis: Channel level (short circuit, open circuit, overload)
Fault Behavior: Single-channel fault does not affect other channels, system alarm and recording
Safety Mechanism: Output circuit redundancy detection, output cut-off to safe state when faulty
V. Usage Tips (Installation / Wiring / Configuration)
Installation: Insert into the F3 rack backplane slot, snap lock; leave 20mm clearance for heat dissipation, away from strong electricity / frequency interference.
Power Supply: 24VDC regulated power supply, positive and negative terminals; FG protective ground reliably grounded.
Output Wiring: 16 DO channels connected to field devices (electromagnetic valve / relay coil positive pole), common terminal connected to 24VDC negative pole; single channel ≤ 0.5A.
Configuration (SILworX): Add F3322 to hardware; define channel usage, fault response; compile and download.
Maintenance: Regularly check terminals, LEDs; faults located through software; supported hot swap replacement.
Compatibility: Can be paired with F3311/F3313/F3318 CPUs and F32xx DI modules in the same rack; configuration needs to be updated when replacing.