F3313
May 14, 2026

F3313

I. Basic Information Model: F3313 (Full Order Number: F3313316) Brand: HIMA Black Horse Series: HIMatrix F3 Type: SIL3 Safety CPU/Controller, TMR Triple Redundancy Application: SIS, ESD, BMS, F&G Software: SILworX Safety Level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e Architecture: Triple Modular Redundancy TMR (3×CPU Voting) Status: In Production

Description

I. Basic Information

Model: F3313 (Full Order Number: F3313316)

Brand: HIMA Black Horse

Series: HIMatrix F3

Type: SIL3 Safety CPU/Controller, TMR Triple Redundancy

Application: SIS, ESD, BMS, F&G

Software: SILworX

Safety Level: SIL3 (IEC 61508), TÜV AK6, Cat.4/PL e

Architecture: Triple Modular Redundancy TMR (3×CPU Voting)

Status: In Production

II. Hardware Parameters

Power Supply: 24VDC, -15% to +20%

Power Consumption: Approximately 15W

Processor: 3 × 32-bit secure CPU (same as F3311)

Memory: 1MB Flash (program) + 1MB SRAM (data)

Isolation: Channel-to-channel / Ground 2kVrms

Temperature: 0℃ to +60℃ (operation); -40℃ to +85℃ (storage)

Protection: IP20

Size: 25mm × 203mm × 127mm

Weight: Approximately 0.8kg

Hot Swap: Supported

III. Interfaces

Ethernet: 2 × RJ45 10/100Mbps (with switch)

Serial Port: 1 × RS485 (terminal)

Local Channel: 4 configurable secure channels (DI/DO logic)

IV. Performance and Security

Response Time: ≤ 10ms

Self-Diagnosis: Full coverage (power supply, backplane, communication, circuit, logic)

Fault Behavior: Automatically enter safe state, single-channel failure does not stop operation

Redundancy: TMR three-out-of-two, fault-tolerant operation

V. Usage Tips (Installation / Wiring / Configuration / Maintenance)

Installation: Standard DIN rail or F3 rack backplane slot, push in the latch to lock; leave a gap for heat dissipation, keep away from strong electricity / frequency conversion interference.

Power Supply: 24VDC regulated power supply, positive and negative terminals; FG protective ground must be reliably grounded.

Communication:

Ethernet: Directly connect to the switch / PC, default IP 192.168.0.1, used for downloading / monitoring / configuration.

RS485: Connect according to A/B polarity, to the instrument / third-party serial port device.

Configuration (SILworX): New project selection F3313; configure IP, protocol, redundancy, interlock logic; compile and download, online monitoring.

Maintenance: Regularly check power supply, contact, wiring; check the panel lights + software diagnosis for faults; support hot swap replacement without downtime.