F3222
Description
I. Basic Information
Model: F3222
Series: HIMA F3 (19" Rack-mounted Safety SIS System)
Type: 16-channel DI Safety Digital Input Module
Safety Level: SIL3 (IEC 61508), TÜV Certification, Cat.4/PL e
Programming Software: ELOP II
Status: Out of Production (EOL), Only Second-hand / In Stock / Reconditioned Items
II. Electrical Specifications
Channels: 16 digital inputs (DI)
Input signals: 24VDC dry contacts or 8mA sensor signals
Isolation: Safety isolation 2kVrms
Response time: Typical 10ms
Power supply: Backplane 5VDC (70mA) or external 24VDC (130mA)
Diagnosis: Open circuit / short circuit detection, LED status indication
Environment: 0℃~+60℃, IP20
Size/Weight: 19" rack, 4TE width; approximately 0.1kg
III. Differences from Modules in the Same Series
F3221/F322116: 16 DI, isolation 2kV, response 10ms
F3222: 16 DI, enhanced channel diagnosis, compatible with F3112/F3113A
F3113A: 16 DI, basic model, isolation 1kV
IV. Alternative Suggestions
Direct replacement: F322116 (same specification 16DI, fully compatible)
Module replacement: F3DIO8/801 (8DI + 8DO, SIL3, DIN rail)
System upgrade: HIMatrix F35 or HIMax (SILworX, modern communication)

Get a Quote