F3001
Description
F3001 (written as F30 01 in standard form) is a compact safety controller (CPU + integrated I/O) of the HIMatrix F30 series from German HIMA (Black Horse). It features 20 DI inputs and 8 DO outputs, is SIL3 certified, and is used in SIS/ESD systems. It is currently a mainstream product available for purchase.
I. Basic Information
Model: F3001 (F30 01)
Series: HIMA HIMatrix F30 (High-end Compact Safety Controller)
Type: CPU + Integrated DI/DO, can operate independently or serve as a system controller
Safety Level: SIL3 (IEC 61508/61511), TÜV Certification; Cat.4/PL e (EN ISO 13849-1); Rail Transportation SIL4 (EN 50126/50128/50129)
Programming Software: ELOP II Factory (native); OS V7 + compatible with SILworX
Status: In-service mainstream, available for normal purchase
II. Integrated I/O Specifications
Digital Input DI: 20 channels
Signal: 24VDC (high level 15–30V, low level ≤5V), source type / sink type compatible
Input current: ≥2mA@15V; ≤1.5mA@5V
Isolation: Non-isolated between channels, safety isolation on system side
Diagnosis: Short circuit / open circuit detection, with LED status indicator
Digital Output DO: 8 channels
Voltage: ≥L+ - 2V; load 24VDC
Current: Channels 1–3/5–7: 0.5A (≤60℃); channels 4/8: ≤50℃ when 2A, 50–60℃ when 1A
Protection: Short circuit / overload / overtemperature automatic shutdown, fail-safe design
Diagnosis: Load monitoring, short circuit reporting, with LED status indicator
III. Hardware and Performance
Processor: Dual-core redundant safety architecture, hardware-level fault tolerance
Memory: User program ≤1023kB, user data ≤1023kB (OS V7+)
Response time: ≥20ms; scan cycle configurable
Communication: 4×RJ45 (10/100Mbps, integrated switch); supports SafeEthernet, Modbus TCP, Profinet, EtherNet/IP; 3×9-pin D-sub fieldbus interface (FB1/FB2 expandable, FB3 standard RS485)
Power supply: 24VDC (18–30VDC), no-load 0.5A, full load ≤8A; external 10A delay fuse
Environment: 0℃~+60℃ (standard type); -20℃~+60℃ (F30 011); -25℃~+70℃ (F30 014, rail transit grade)
Size / Weight: 257×114×66mm; approximately 1.2kg
Installation: Standard 35mm DIN rail; protection class IP20
IV. Safety and Diagnosis
Architecture: Dual-core redundant + cyclic self-check (hardware, voltage, I/O, communication), compliant with SIL3 integrity
Diagnosis: Full coverage (DI short circuit / open circuit, DO overload / short circuit, CPU / communication failure); FAULT light on when fault occurs and fault code output
MTTFd: 1500,000 hours, low-risk failure probability
Certification: TÜV, CE, Ex nA II T4 X (usable in Zone 2 explosion-proof area)
V. Typical Applications
Petrochemical: ESD emergency stop, valve interlock, pump / fan safety control, F&G fire gas detection
Power: Boiler / turbine protection, gas turbine control, auxiliary machine interlock
Oil and Gas: Offshore platform SIS, station emergency shutdown, pressure / level interlock
Rail Transit: On-board safety control, signal system (F30 014 dedicated)

Get a Quote