SCXI-1126 | NI 8-Channel Isolated Frequency Input Module
Description
Part Code Definition
SCXI = NI SCXI modular signal conditioning system platform
1126 = 8-channel isolated frequency input dedicated model code
Technical Specifications
Channel:8 independent isolated differential input channels
Frequency range:10 programmable spans:250Hz/500Hz/1kHz/2kHz/4kHz/8kHz/16kHz/32kHz/64kHz/128kHz
Isolation rating:250Vrms channel-to-chassis & channel-to-channel isolation; max input withstand 1000VDC transient overvoltage protection
Trigger setting:Threshold:-0.5~+4.5V adjustable; Hysteresis:0~4.98V software configurable per channel
Filter:4-order low-pass filter, optional cutoff:1Hz/40Hz/320Hz/1kHz per channel
Max scan rate:333kS/s full module multiplex output sampling
Operating ambient:0℃~+50℃ operation, -40℃~+70℃ storage, RH5%~95% non-condensing
Dimension:standard SCXI form factor 173×86×203mm
Interface & Communication Configuration
Front I/O:32pin DIN connector, matching terminal accessories SCXI-1305(BNC type)/SCXI-1320(screw terminal type) for field sensor wiring
Rear bus:standard SCXI backplane golden finger, plug into chassis slot, module data multiplex to single DAQ AI channel via internal SCXI bus, controlled by PCI/PCIe NI DAQ board
Output mode:Multiplex(default)/Parallel dual output configurable via LabVIEW/NI-DAQmx software
Core Functions
Isolate field frequency/pulse signal to eliminate ground loop interference between field equipment and cabinet DAQ system
Convert input frequency signal into proportional DC analog voltage via F/V conversion for standard DAQ analog acquisition
Software independent parameter setup for every channel: frequency span, trigger threshold, anti-jitter hysteresis, noise filter cutoff
Multiplex all 8-channel converted analog signals into single DAQ input channel to save DAQ hardware resource
Overvoltage protection prevents module damage from field surge voltage
Application Scenarios
Turbine speed pickup sensor acquisition, flowmeter pulse signal collection, encoder frequency measurement, motor rotation speed monitoring, industrial bench vibration frequency test, legacy SCXI DAQ system spare replacement
Operation & Maintenance Notes
Power off chassis before hot plug/unplug module; use shielded twisted pair for field frequency wiring to reduce EMI interference; configure corresponding frequency range & filter parameter according to sensor nominal output frequency in DAQ software; regularly fasten terminal block screws to avoid loose contact; keep chassis ventilation free from dust buildup.