SCXI-1124 | NI 6-Channel Isolated Analog Output DAC Module
Description
Part Code Definition
SCXI = NI SCXI signal conditioning chassis platform
1124 = 6-channel isolated DAC analog output module model, fixed 12-bit resolution architecture.
Technical Specifications
Channel count:6 fully independent galvanic isolated output channels
DAC resolution:12-bit per channel
Voltage output ranges:Unipolar:0~1V/0~5V/0~10V; Bipolar:±1V/±5V/±10V, max single channel drive 5mA; series-connected channels up to 60VDC total output
Current output:0~20mA per channel fixed range
Update rate:Single channel max 555S/s; full 6-channel simultaneous 125S/s per channel
Isolation rating:250Vrms channel-to-backplane galvanic isolation
Onboard storage:EEPROM for saving calibration coefficient
Operating temperature:0℃~+50℃ operation, -40℃~+70℃ storage, RH5%~95% non-condensing
Dimension:Standard SCXI module 173×86×203mm, standard chassis slot installation
Certification:CE, UL certified
Interface & Communication Configuration
Front terminal:96-pin DIN connector, pairing SCXI-1324 screw terminal accessory for field actuator wiring
Rear interface:SCXI standard golden finger backplane, plug into SCXI chassis slot, digital command transmitted via SCXI internal bus from PCI/PCIe NI DAQ control card
Control mode:Digital bus control by host DAQ card, multiple SCXI-1124 cascaded in one chassis under single DAQ controller
Core Functions
Convert digital control command from DAQ system into isolated analog voltage/0~20mA current signal for field actuator drive
Per-channel independent isolation eliminates ground loop interference between control cabinet and field equipment
Software flexible channel mode switching between voltage/current output via LabVIEW/NI-DAQmx configuration
Built-in stored calibration data guarantees long-term output precision without frequent field recalibration
Multi-module stacking expands total analog output quantity for large-scale distributed process control
Application Scenarios
Industrial test bench servo valve analog control, environmental chamber heater/damper regulation, chemical plant PID analog output control, legacy SCXI DAQ system spare replacement, lab precision power source analog setting output.
Operation & Maintenance Notes
Cut off chassis power before plug/unplug module; use shielded twisted wire for field output wiring to reduce EMI drift; match output range with actuator rated input in DAQ software; periodically inspect terminal screw tightness to avoid open circuit; keep module ventilation free from dust accumulation.