II. Product Parameters
Model: 490NRP95400
Protocol: S908 RIO (Quantum-specific Remote I/O Protocol)
Electrical Interface: 1×F-type (Coaxial, RIO Bus)
Optical Interface: 2×ST optical interface (Transmit and Receive are Independent)
Optical Fiber Type: Multimode (62.5/125μm) / Single-mode (9/125μm)
Transmission Distance: Multimode 2km; Single-mode up to 20km
Power Supply: 24 VDC (19.2–30 VDC) or 115/230 VAC
Power Consumption: ≤8 W
Weight: Approximately 1.5 kg
Size: 168 × 119 × 56 mm
Operating Temperature: −20℃ ~ +60℃
Certifications: CE, UL, CSA, RoHS
III. Product Specifications
Type: S908 RIO Optical Splitter Repeater (Passive Signal Forwarding, No Delay)
Topology: Point-to-Point, Bus Type (Multiple Repeater Cascade)
Isolation: Complete Photoelectric Isolation, Eliminating Ground Potential Difference and EMI Interference
Installation: Panel / Rack Installation, IP20 Protection
Diagnosis: LED Indicators (Power Supply, Transmit and Receive, Fault)
IV. Series
Series归属: Modicon 490 Communication Series → NRP (Network Repeater) Sub-Series
Same Series Positioning:
490NRP25300/25400: Modbus Plus (MB+) Optical Repeater
490NRP95400: S908 RIO Specialized Optical Repeater (Quantum Platform)
V. Features
✅ S908 RIO Specific: Compatible with Quantum Native Remote I/O Bus, Seamless Compatibility
✅ Ultra-long Distance: Single-mode optical fiber up to 20km, Breaking through the 100m limit of coaxial cable
✅ Passive Low Delay: Direct Signal Forwarding, No Protocol Conversion, Zero Extra Delay
✅ Strong Anti-interference: Photoelectric Isolation, Resisting Strong Electromagnetic Noise from Frequency Converters, Motors, etc.
✅ Flexible Power Supply: Supports AC/DC Dual Power Supply, Suitable for Different On-site Power Conditions
VI. Applications
Extend the communication distance of S908 RIO bus, connect remote I/O stations across workshops / factories
Electrical Isolation: Eliminate Ground Potential Difference, Protect Quantum PLC and Remote I/O Modules
Build Optical RIO Network, Replace Interfered Coaxial Cables
Bus Cascade: Connect multiple repeaters in series to expand large-scale distributed I/O system
VII. Application Domains
Power Energy: Power Plant DCS, Generator Control, Remote I/O Monitoring
Petrochemical: Refining Plants, Explosion-proof Areas, Long-distance Pipeline Monitoring
Metallurgy and Steel: Blast Furnaces, Rolling Mills, Continuous Casting Lines, etc. Strong Interference Environment
Water Treatment: Sewage Plants, Pump Stations Distributed I/O Control System
Large-scale Manufacturing: Automotive, Building Materials, etc. Workshop-level Remote I/O Communication