Honeywell 51304648-125 (MU-TDOA13)
May 28, 2026

Honeywell 51304648-125 (MU-TDOA13)

51304648-125 (MU-TDOA13) is a 16‑channel AC solid‑state relay (SSR) digital output FTA for Honeywell TPS/TDC3000/Experion PKS (UCN) DCS systems. It drives 120/240 VAC loads and mates with MU/MC‑PDOX01/02 IOPs.

Description

Product Overview

51304648-125 (MU-TDOA13) is a 16‑channel AC solid‑state relay (SSR) digital output FTA for Honeywell TPS/TDC3000/Experion PKS (UCN) DCS systems. It drives 120/240 VAC loads and mates with MU/MC‑PDOX01/02 IOPs.

Model Definition

  • 5130: Honeywell TPS/TDC3000/Experion PKS series

  • 4648: AC digital output (DO) FTA family

  • 125: Hardware revision R125, CE‑certified, non‑conformal coated, crimp‑terminal version (MU-TDOA13).

Technical Specifications

  • Channels: 16 DO, SSR (solid‑state relay) type

  • Load voltage: 120/240 VAC

  • Load current: 2.5 A max per channel

  • Isolation: Channel‑to‑ground (no channel‑to‑channel)

  • Backplane power: 24 VDC ±10%

  • Terminals: Crimp (compression) type

  • Fuses: 2.5 A SB per channel

  • Size: 12 in (307 mm, Size B)

  • Coating: No conformal coating

  • Certification: CE

  • Redundancy: Not supported

  • Hot swap: Supported

Interface & Features

  • System side: UCN backplane I/O bus, compatible with PDOX01/02 IOP

  • Field side: 16 independent (common/NO/NC) crimp terminals

  • Diagnostics: Board‑level fault detection (no per‑channel)

  • Key advantage: SSR, no mechanical contacts → fast response, long life for AC loads; CE compliance for global deployment.

51304648 AC FTA Series Comparison

Part NumberAliasOutputVoltageTerminalsCoatingCE
51304648‑100MU‑TDOA13SSR (AC)120/240 VACCrimpNoNo
51304648‑125MU‑TDOA13SSR (AC)120/240 VACCrimpNoYes
51304648‑175MC‑TDOA13SSR (AC)120/240 VACCrimpYesYes
51304648‑200MU‑TDOA52SSR (AC)120/240 VACScrewNoNo
51304648‑225MU‑TDOA53SSR (AC)120/240 VACScrewNoYes
51304648‑275MC‑TDOA53SSR (AC)120/240 VACScrewYesYes

Applications

  • Systems: Honeywell TPS, TDC3000, Experion PKS (UCN)

  • Industries: Petrochemical, power, water treatment, general manufacturing

  • Typical loads: 120/240 VAC solenoids, motor starters, heaters, alarm lamps

Installation & Maintenance

Installation

  1. Insert into standard DCS I/O slot (Size B)

  2. Lock backplane connector to PDOX01/02 IOP

  3. Field AC devices to crimp terminals

  4. Configure in system software

Maintenance

  • Quarterly: Check terminal crimp tightness and oxidation

  • Verify SSR status via system diagnostics

  • Store spares in anti‑static bags, dry environment