12P1064X122
Description
1. Product Overview
2. Main Features
Hybrid I/O Integration: 4AI / 2AO / 8DI / 4DO integrated design
Analog Signal Compatibility: 4~20mA current / 0~10V voltage, software‑selectable
High Precision: 16‑bit ADC/DAC, ±0.1% full‑scale accuracy at 25°C, low temperature drift
Software Configurable: Signal type, engineering range, digital filter, and working mode fully configurable
Industrial Protection: 1500VDC isolation, overvoltage, overcurrent, short‑circuit, and overtemperature protection
Communication: Standard RS485, Modbus RTU; baud rates 9600/19200/38400bps
Wide Temperature Range: -25°C ~ +60°C operating temperature
Digital Channel Flexibility: NPN/PNP logic support, 0~500ms adjustable debounce time
Fail‑Safe Operation: Analog channels with digital filtering and communication‑loss fail‑safe mode
Durable Construction: Flame‑retardant plastic housing, compact, low power consumption
Easy Installation: 35mm standard DIN rail mounting, simple wiring and maintenance
3. Technical Specifications
3.1 General Parameters
Model: 12P1064X122
Rated Power Supply: 24VDC ±10%
Max Working Current: ≤300mA
Isolation Voltage: 1500VDC (field side to internal circuit)
Operating Temperature: -25°C ~ +60°C
Storage Temperature: -40°C ~ +85°C
Relative Humidity: 5% ~ 95% RH, non‑condensing
Mounting: 35mm standard DIN rail
Housing Material: Industrial flame‑retardant engineering plastic
3.2 Channel Configuration
Analog Input (AI): 4 channels, 4~20mA / 0~10V software‑selectable
Analog Output (AO): 2 channels, 4~20mA / 0~10V software‑selectable
Digital Input (DI): 8 channels, 24VDC level compatible
Digital Output (DO): 4 channels, 0.5A rated load per channel
3.3 Analog Performance
Resolution: 16‑bit
Basic Accuracy: ±0.1% full scale at 25°C
Temperature Drift: ±0.2% full scale over full temperature range
AI Input Load: Current ≤250Ω; Voltage ≥100kΩ
AO Output Load: Current ≤500Ω; Voltage ≥1kΩ
3.4 Communication Parameters
Interface: RS485
Protocol: Modbus RTU
Default Baud Rate: 9600bps
Data Format: 8 data bits, 1 stop bit, no parity
Device Address: 1~247 configurable
4. Safety Precautions
Installation, wiring, and maintenance must be performed by qualified professional technicians.
Disconnect all power before wiring, disassembly, or maintenance to avoid electric shock and module damage.
Do not install in flammable, explosive, dusty, or corrosive environments.
Maintain adequate ventilation; do not block heat dissipation holes.
Separate power and signal cables during wiring to reduce electromagnetic interference.
Connect the protective grounding terminal to reliable earth ground.
Do not exceed the rated voltage, current, or load of each channel.
Do not disassemble or modify the internal circuit without authorization.
5. Installation and Terminal Definition
5.1 DIN Rail Installation
Secure a 35mm standard DIN rail firmly on the mounting panel.
Hook the module’s upper buckle onto the DIN rail edge.
Press downward until the bottom lock clicks into place.
Shake gently to confirm firm installation without loosening.
5.2 Terminal Pin Assignment
24VDC Positive
24VDC Negative
AI1+
AI1−
AI2+
AI2−
AI3+
AI3−
AI4+
AI4−
AO1+
AO1−
AO2+
AO2−
DI Common
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
DO1
DO2
DO3
DO4
DO Common
Protective Ground (PE)
5.3 Wiring Instructions
Strip approximately 6mm of insulation from wire ends.
Loosen terminal screws and insert wires into corresponding terminals.
Tighten screws moderately to ensure good contact (avoid over‑tightening).
Analog signals: Use shielded twisted‑pair cable with single‑end grounding.
Power/digital signals: Use stranded copper wire of appropriate gauge.
Secure cables with ties to avoid tension on terminals.
6. Parameter Configuration
6.1 Connection Method
6.2 Configurable Parameters
Analog Input: Signal type selection, custom engineering range, digital filter adjustment
Analog Output: Signal type selection, output calibration, fail‑safe mode (fixed/hold)
Digital Input: NPN/PNP logic, debounce time (0~500ms)
Digital Output: Output logic, communication‑loss fail‑safe ON/OFF, pulse output settings
Communication: Baud rate, Modbus address, restore factory defaults
6.3 Save and Activation
7. Operation Description
7.1 Power‑On Self‑Test
7.2 Main Functions
Analog Input: Collect sensor analog signals, convert to digital data, and upload to the control system.
Analog Output: Receive control commands and output standard analog signals to drive valves/actuators.
Digital Input: Detect switch/sensor on/off status and upload state changes.
Digital Output: Control external relays, solenoid valves, and indicator lights.
Communication: Exchange data and configure parameters with the host/PLC via Modbus RTU.
7.3 Indicator Status
Power LED Steady Green: Power normal
Power LED Off: No power or power fault
Status LED Green Flashing: Normal operation and communication
Status LED Red Flashing: Overload, short circuit, or communication error
Status LED Steady Red: Hardware failure (replace module)
8. Daily Maintenance
Regularly check terminal tightness to prevent oxidation and loose contacts.
Clean dust with a dry soft cloth only (no liquid or chemical solvents).
Maintain operating temperature and humidity within specified ranges.
Replace aging or damaged cables promptly.
Recalibrate channels if sampling data is unstable or inaccurate.
9. Troubleshooting
- Power Indicator Off
Cause: No 24VDC input, reversed polarity, or broken wire
Solution: Check power wiring and correct polarity
- Communication Failure
Cause: Baud rate/address mismatch, RS485 A/B reversed, missing 120Ω terminal resistor
Solution: Unify parameters, adjust wiring, add terminal resistor
- Analog Input Unstable
Cause: Loose terminals, wrong signal range, or electromagnetic interference
Solution: Fasten wiring, confirm signal type, use shielded cable and proper grounding
- Analog Output Inaccurate
Cause: Range error or load resistance mismatch
Solution: Recalibrate range and match load parameters
- Digital Input No Response
Cause: Loose wiring or logic setting error
Solution: Check wiring and adjust NPN/PNP logic
- Digital Output No Action
Cause: Overload or incorrect logic mode
Solution: Reduce load to rated range and reconfigure