9907-147
Description
Core Functions
Dual control modes: isochronous (constant‑speed) for single‑unit stable operation; droop mode for multi‑genset parallel load balancing.
Reverse‑acting logic: Fuel increases as control signal decreases; failsafe to full‑fuel position on power loss, compatible with hydraulic/electro‑hydraulic heavy‑duty actuators.
Analog PID closed‑loop control with startup ramp, actuator stroke limit, load rejection protection and overspeed test function.
High‑voltage power input (88‑132 VAC / 90‑150 VDC), suitable for harsh industrial power supply environments.
Supports real‑kW load sharing signal, 4‑20 mA remote setpoint, and RS‑485 Modbus‑RTU communication for remote monitoring & parameter configuration.
Electrical Specifications
Power Supply: 88‑132 VAC / 90‑150 VDC (high‑voltage version)
Power Consumption: ≤15 W
Speed Input: Magnetic Pickup (MPU), switch‑selectable ranges: 500‑1500Hz / 1000‑3000Hz / 2000‑6000Hz / 4000‑12000Hz
Actuator Output: 0‑200 mA proportional current (reverse‑acting)
Communication: RS‑485 Modbus‑RTU
Operating Temperature: −40 °C ~ +65 °C
Storage Temperature: −55 °C ~ +105 °C
Certifications: UL Listed E97763, MIL‑STD‑461C, CE, Class I Div 2 hazardous area compliant
Mechanical & Environmental Features
Mounting: Front panel‑mount
Enclosure: NEMA 4X / IP54 metal housing, dust‑proof, vibration‑resistant, corrosion‑resistant
Weight: ~4.4 kg (9.7 lbs)
Vibration & shock resistance meets MIL‑STD‑810 standards for marine and industrial harsh environments
Typical Applications
Multi‑generator parallel control for thermal power plants and emergency power stations
Gas/steam turbine governing and load control systems
Marine main engine speed regulation and propulsion control
Oil‑gas field compressor engine and prime‑mover control systems
Get a Quote