9905-068
Description
Core Functions
Two control modes: isochronous (constant speed) for single‑unit operation; droop for parallel gensets.
Forward‑acting output logic, compatible with standard proportional electric‑hydraulic actuators.
PID closed‑loop control with startup ramp, stroke limit, overspeed test and protection.
Accepts 4‑20 mA remote setpoint signal for speed adjustment, compatible with DCS/PLC.
RS‑485 Modbus‑RTU communication for monitoring and parameter tuning.
Electrical Specifications
Power Supply: 18–40 VDC (nominal 24 VDC)
Speed Input: Magnetic pickup (MPU)
Actuator Output: 0–200 mA proportional current
Communication: RS‑485 Modbus‑RTU
Certifications: CE, Class 1 Div 2 hazardous area compliant
Environmental & Mechanical Features
Operating Temperature: −40 °C ~ +85 °C
Mounting: Front panel‑mount
Enclosure: Rugged metal housing, dust‑proof and vibration‑resistant
Typical Applications
Speed control for engine‑driven generator sets
Gas turbine governing systems
Marine power unit speed regulation
Oil‑gas industrial prime‑mover control