9907-624
Description
Core Functions
Dual control modes: isochronous mode for single‑unit constant‑speed operation; droop mode for multi‑unit genset parallel load sharing.
PID closed‑loop control with startup ramp, actuator stroke limit, load rejection protection, overspeed test and fuel limiting function.
Supports 4‑20 mA / 1‑5 VDC analog remote speed/load setpoint input for external DCS/PLC system control.
Forward‑acting control logic, compatible with proportional electric/hydraulic actuators.
RS‑485 Modbus‑RTU communication for real‑time monitoring and parameter configuration.
Electrical Specifications
Power Supply: 18–40 VDC (nominal 24 VDC)
Speed Input: Magnetic pickup (MPU), wide frequency range
Actuator Output: 0–200 mA proportional current output
Communication: RS‑485 Modbus‑RTU protocol
Control Precision: ±0.25% steady‑state speed regulation accuracy
Certifications: CE compliant, industrial anti‑interference standard
Environmental & Mechanical Features
Operating Temperature: −40 °C ~ +85 °C
Mounting: Front panel‑mount installation
Enclosure: Rugged metal housing, dust‑proof and vibration‑resistant
Typical Applications
Speed‑load control for diesel/gas engine‑driven generator sets
Industrial steam/gas turbine governing systems
Marine multi‑genset parallel power control
Petrochemical and oil‑gas prime‑mover safety control
Get a Quote