9907-164
Description
Core Functions
Dual control modes: isochronous mode for single‑unit constant‑speed operation; droop mode for multi‑unit parallel load sharing.
Triple‑loop PID control: speed, load, auxiliary/cascade pressure regulation, with critical speed avoidance function.
Built‑in startup ramp, warm‑up control, load rejection protection, overspeed test and zero‑speed detection.
On‑panel keypad & 2‑line display for local parameter configuration, real‑time monitoring and fault logging.
Supports Modbus‑RTU/ASCII communication and 4‑20 mA analog signals for seamless DCS/PLC integration.
Electrical Specifications
Power Supply: 18–32 VDC (nominal 24 VDC, 1A)
Speed Input: Magnetic pickup (MPU), 0.5–25000 Hz frequency range
I/O Configuration: 6 analog inputs, 6 analog outputs, 16 discrete inputs, 8 relay outputs
Communication: RS‑232, RS‑422/485, dual‑port Modbus protocol
Control Precision: ±0.25% steady‑state speed regulation accuracy
Certifications: CE, UL, Class 1 Div 2 hazardous area compliant
Environmental & Mechanical Features
Operating Temperature: −40 °C ~ +70 °C
Protection Grade: IP56 (front panel), IP20 (rear terminals)
Mounting: Front panel‑mount
Dimensions: 355.6 × 279.4 × 101.6 mm (14×11×4 inch)
Weight: Approx. 4.13 kg
Typical Applications
Speed‑load control for industrial steam/gas turbines
Utility power plant turbo‑generator governing systems
Petrochemical & oil‑gas compressor drive turbines
Turboexpander and heavy‑duty prime mover safety control
Get a Quote