9905-967
Description
Core Functions
Two control modes: isochronous mode for single‑unit constant‑speed operation; droop mode for multi‑unit parallel load sharing.
PID closed‑loop control with critical speed avoidance, valve stroke limitation, startup ramp control and load rejection protection.
Independent overspeed monitoring, real‑time self‑diagnosis, fault recording and multi‑channel relay alarm outputs.
4‑20 mA analog remote setpoint input, compatible with upper‑level DCS/PLC systems.
Local parameter configuration and online tuning via dedicated Woodward software.
Electrical Specifications
Power Supply: 24 VDC (wide‑range: 18–40 VDC)
Speed Input: Magnetic Pickup (MPU) sensor signal
Actuator Output: PWM drive signal for hydraulic/electric actuators
I/O: Programmable 4‑20 mA analog I/O, multi‑channel digital contact I/O
Communication: RS‑232 / RS‑485, Modbus‑RTU protocol
Safety Certification: Class 1 Div 2 hazardous area certified, industrial‑grade anti‑interference
Environmental & Mechanical Features
Operating Temperature: −40 °C ~ +85 °C
Mounting: Panel‑mount installation
Enclosure: Rugged metal housing, dust‑proof and corrosion‑resistant
Typical Applications
Speed‑load control of engine and turbine generator sets
Power plant, petrochemical and oil‑gas compressor control systems
Marine auxiliary power generation prime mover control
Industrial prime mover governing and safety protection systems
Get a Quote