5463-124
Description
Key Features
Dual control modes: Isochronous (zero droop) for standalone constant speed; droop control for grid parallel and load sharing.
High accuracy: Speed regulation ±0.25%; adaptive PID; speed input 0.5–32,000 Hz.
Flexible setpoint: Accepts 4–20 mA or 1–5 Vdc analog signals for remote speed/load setpoint.
I/O: 2 × MPU/proximity speed inputs; 8 analog in (4–20 mA), 20 discrete in; 2 actuator out (4–20/200 mA), 8 relay out.
Protection: Overspeed trip, critical speed avoidance, soft start, valve limiting, 15 fault shutdown + 15 alarm inputs, first‑out logging.
Communications: RS‑232/RS‑485 (Modbus RTU/ASCII); password‑protected configuration.
Rugged: IP20; –40 °C to +70 °C; CE/UL certified; SIL2 capable.
Specifications
Brand/Model: Woodward 5463-124 (505 Series)
Power supply: 18–32 VDC (24 VDC nominal)
Speed input: 2 × MPU/proximity, 0.5–32,000 Hz
Analog I/O: 8 × 4–20 mA in; 2 × 4–20/20–200 mA out
Discrete I/O: 20 × in; 8 × relay out (5 A/24 VDC)
Communication: RS‑232/485, Modbus RTU/ASCII
Operating temperature: –40 °C to +70 °C
Certifications: CE, UL, SIL2
Applications
Turbines: Steam/gas turbine speed/load control and overspeed protection.
Generators: Diesel/gas gen‑sets, islanded/grid‑connected power plants.
Compressors: Industrial compressors in oil & gas and process industries.
Get a Quote