171CCC78010
Description
1. General Description
2. Product Identification
Model: 171CCC78010
Manufacturer: Schneider Electric
Series: Modicon Momentum
Type: M1/M1E Processor Adapter (2×Modbus, 32 MHz)
Compatibility: Modicon Momentum I/O bases, M1/M1E processors
Status: Discontinued (replaced by 171CBU78090)
Country of Origin: France
UPC: 785901328575
3. Technical Specifications
Processor & Memory
Processor: X86‑based, 32 MHz
Flash Memory: 512 kB
RAM: 512 kB
Program Memory: 18 kB (LL984), 240 kB (IEC)
Data Memory: 24 kB
Scan Time: 1 ms per kB
I/O Capacity
Discrete I/O: 8192 inputs / 8192 outputs
Register I/O: Up to 26,048 words
Communication
Ports:
1 × Non‑isolated RS‑232C (Modbus RTU/ASCII)
1 × Isolated RS‑485 (Modbus RTU/ASCII)
1 × I/O Bus (to Momentum I/O base)
Protocols: Modbus RTU/ASCII, IEC 61158 (I/O Bus)
Electrical
Supply Voltage: 5 V DC ±5%
Power Consumption: ≤ 12 W
Environmental
Operating Temperature: −25 °C to +70 °C
Storage Temperature: −40 °C to +85 °C
Humidity: 5–95% RH (non‑condensing)
Vibration: IEC 60068‑2‑6 compliant
Material: Lexan (industrial polycarbonate)
Physical
Dimensions (H × W × D): 25 mm × 125 mm × 183 mm
Weight: 0.215 kg
4. Key Features
Dual Modbus Ports: RS‑232 + isolated RS‑485 for multi‑drop networks
Large I/O Support: 8192 discrete + 26k register I/Os for complex systems
Extended Memory: 512 kB Flash/RAM, 240 kB IEC program space
Legacy Compatibility: Connects M1/M1E CPUs to Momentum I/O bases
Industrial Grade: Wide temperature range, shock/vibration resistant
Software Support: Concept ≥ V2.5 SR1, Modsoft ≥ V2.5, ProWORX 32/NxT
5. Applications
Migration of M1/M1E systems to Modicon Momentum I/O
High‑I/O discrete/register control (material handling, packaging, textiles)
Multi‑node Modbus networks (RS‑232 local, RS‑485 remote I/O)
Retrofit projects reusing M1/M1E processors with modern I/O
6. Installation Instructions
Power Off: Disconnect all power to the M1/M1E processor and Momentum I/O base.
ESD Protection: Use anti‑static wristband when handling the adapter.
Adapter Insertion: Align 171CCC78010 with M1/M1E processor expansion slot; press firmly until fully seated.
Base Mounting: Attach adapter‑processor assembly to Momentum I/O base via I/O Bus connector; tighten mounting screws.
Wiring:
RS‑232: Connect to HMI/PC (3‑wire: TX, RX, GND).
RS‑485: Connect to Modbus network (2‑wire + shield, 120 Ω termination at bus ends).
Power Up: Apply 5 V DC; check LED indicators (PWR green, RUN green, FLT red).
Configuration: Use Concept/Modsoft/ProWORX to set I/O mapping, Modbus addresses, baud rates (9.6k–115.2k), and protocol modes.
7. Compatibility
Processors: M1/M1E series
I/O Bases: All Modicon Momentum discrete I/O bases (170XTS00100 series)
Software: Concept ≥ V2.5 SR1, Modsoft ≥ V2.5, ProWORX 32, ProWORX NxT V2.0
8. Safety & Handling
Installation/maintenance only by qualified personnel per local electrical codes.
Disconnect power before wiring or maintenance to avoid electric shock.
Avoid water, moisture, corrosive substances, and direct sunlight.
Use ESD protection to prevent static damage to electronic components.
9. Maintenance & Troubleshooting
Visual Inspection: Quarterly check for cracks, loose screws, or damaged connectors.
Cleaning: Use dry, lint‑free cloth only; no solvents.
Common Issues:
PWR Off: Check 5 V DC supply and connections.
FLT On: CPU fault; re‑seat adapter, check I/O base, reload program.
Modbus Communication Fail: Verify wiring, termination, baud rate, address, and protocol.
I/O Mismatch: Recheck software I/O mapping and base configuration.
Get a Quote