170XTS04200
Description
1. General Description
2. Product Identification
Model: 170XTS04200
Manufacturer: Schneider Electric
Series: Modicon Momentum / Quantum / Premium
Type: RJ45 termination shunt plug (150 Ω, shielded)
Ports: 1×RJ45 (8P8C, shielded, male)
Function: Bus termination (end‑of‑line), 150 Ω between Data+ / Data−
Cable Compatibility: MB+/RS485 shielded twisted pair
Protection Class: IP20 (inserted)
Material: UL94 V‑0 housing, metal shield
Certifications: CE, UL, CSA, RoHS
Weight: ~0.008 kg (8 g)
Status: Active / available
3. Technical Specifications
Electrical
Termination Resistance: 150 Ω ±5% (between Data+ / Data−)
Protocol: Modbus Plus (1 Mbps), RS485 (half‑duplex)
Contact Rating: 1 A, 50 VDC
Insulation Resistance: ≥500 MΩ
Shielding: 360° metal shield connects to RJ45 pin 7–8
Mechanical
Insertion Cycles: ≥750 (RJ45)
Dimensions: 20 mm × 12.5 mm × 8 mm
Environmental
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5%–95%, non‑condensing
Altitude: Up to 1000 m
4. RJ45 Pinout (Termination Internal Wiring)
Pin 1–2 (Data+) ↔ 150 Ω ↔ Pin 3–6 (Data−)
Pin 4–5: GND (no connection inside plug)
Pin 7–8: Shield (connected to metal shell)
5. Key Features
Precise 150 Ω termination: Matches MB+/RS485 characteristic impedance
Fully shielded: Reduces EMI/RFI at line ends
Plug‑and‑play: No power, no configuration
Compact & lightweight: Fits tight cabinet spaces
Interoperable: Works with 170XTS04100 (T‑connectors) and all MB+/RS485 RJ45 devices
6. Applications
End‑of‑line termination in Modbus Plus/RS485 daisy‑chain networks
Install at the last RJ45 port of the farthest PLC, HMI, or I/O node
Required for 1 Mbps Modbus Plus to avoid data corruption
High‑noise industrial environments (shielded termination)
7. Installation Steps
Power off the network before installation.
Locate the last physical node in the daisy‑chain.
Insert the 170XTS04200 RJ45 male into the unused RJ45 port of the last device.
Ensure the connector clicks and the shield (pins 7–8) makes full contact.
Only one terminator per bus segment (at the far end).
Power on the network and verify communication.
8. Maintenance
Inspect for dirt, bent pins, or damaged shield.
Check continuity: 150 Ω between pins 1–2 and 3–6.
Replace if housing cracked or resistance out of spec.
9. Safety Instructions
Install by qualified personnel.
Disconnect power before wiring.
Avoid liquids, corrosive gases, conductive dust.
10. Troubleshooting
Intermittent communication / high error rate:
Missing or incorrect termination (install 170XTS04200 at last node)
Two terminators installed (remove one)
Shield not continuous (check pin 7–8 contact)
No communication:
Check pinout (Data+ / Data− not reversed)
Verify 150 Ω resistance with multimeter
Get a Quote