170XTS00301
Description
1. General Description
2. Product Identification
Model: 170XTS00301
Manufacturer: Schneider Electric (Modicon)
Product Line: Modicon Momentum (170 Series)
Type: 3‑row spring terminal busbar (connection accessory)
Compatibility: Momentum discrete/analog I/O bases
Termination: Spring clamp (tool‑free)
Rows: 3 horizontal rows
Wire Range: 1 × 2.5 mm² / 2 × 1.5 mm² (copper)
Wire Gauge: AWG 14–18
Color: Gray
Weight: ≈ 0.11 kg
Protection: IP20 (installed)
Status: Active (obsolete per some sources)
3. Technical Specifications
3.1 Electrical
Rated Voltage: 300 VAC
Rated Current: 15 A
Contact Resistance: ≤ 5 mΩ
3.2 Environmental
Operating Temp: −25 °C to +55 °C
Storage Temp: −30 °C to +70 °C
Humidity: 5%–95% (non‑condensing)
Vibration: IEC 60068‑2‑6 (5–200 Hz, 1 g)
Certifications: CE, UL, CSA, RoHS
Material: Thermoplastic (UL 94 V‑0), tin‑plated brass contacts
4. Key Features
Tool‑Free Spring Clamp: Fast insertion, no screwdriver needed; high vibration resistance.
3‑Row Design: Compact common busbar for power distribution and signal grouping.
Broad Compatibility: Fits all Momentum discrete/analog I/O bases.
Snap‑On Mounting: Attaches firmly to I/O base; easy installation/replacement.
Labelable: Front surface for marking I/O points.
Robust Construction: Industrial plastic resists chemicals, oils, and temperature extremes.
5. Applications
Common power distribution for Momentum distributed I/O
Control panels, machine skids, process automation
Material handling, packaging, textile machinery
High‑vibration industrial environments
Retrofit of older Momentum systems
6. Installation Instructions
Power Off: Disconnect all power to the I/O base.
Align Busbar: Match the 170XTS00301 to the base’s connector slots.
Snap Into Place: Press firmly until the busbar clicks and seats flush.
Prepare Wires: Strip 6–7 mm of insulation; use copper wire only.
Insert Wire: Push stripped wire fully into spring terminal; no tool needed.
Verify: Gently tug wire to confirm secure clamping.
Label: Mark terminals per your wiring diagram.
7. Compatibility List
Momentum Discrete Bases: 170ADI/ADO/BDO series
Momentum Analog Bases: 170ANR series
Software: Unity Pro, Concept
8. Maintenance
Quarterly Inspection: Check for loose wires, discoloration, or cracked housing.
Cleaning: Use dry cloth only; avoid solvents.
Replacement: Replace if damaged or corroded.
9. Safety Instructions
Install and service only by qualified electrical personnel.
Always de‑energize the I/O base before wiring or replacing the busbar.
Use copper wire only; do not mix wire sizes in one clamp.
Do not exceed rated voltage/current.
Keep terminals dry and free of conductive debris.
10. Troubleshooting
Loose Connection / Intermittent Signal
Reinsert wire fully into spring terminal.
Check wire insulation length and stripped condition.
Verify no wire strands are outside the clamp.
Cannot Insert Wire
Check wire gauge is within 1.5–2.5 mm².
Ensure spring terminal is not damaged or obstructed.
Busbar Will Not Snap On
Align with base slots correctly.
Check for debris or damage on base connectors.
Get a Quote