170XTS00100
Description
1. General Description
2. Product Identification
Model: 170XTS00100
Manufacturer: Schneider Electric (Modicon)
Product Line: Modicon Momentum (170 Series), Quantum
Type: Screw terminal block (connection accessory)
Compatibility: Discrete I/O bases, analog I/O bases (Momentum/Quantum)
Wire Range: 1 × 2.5 mm² / 2 × 1.5 mm² (copper)
Termination: Screw clamp
Kit Composition: 3 connectors (single row)
Material: Thermoplastic (UL 94 V‑0), tin‑plated brass contacts
Color: Gray
Weight: ≈ 0.1 kg
Protection: IP20 (installed)
Status: Active
3. Specifications
3.1 Electrical
Rated Voltage: 300 VAC
Rated Current: 15 A
Wire Gauge: AWG 14–18 (1.5–2.5 mm²)
Contact Resistance: ≤ 5 mΩ
3.2 Environmental
Operating Temp: −25 °C to +55 °C
Storage Temp: −30 °C to +70 °C
Humidity: 5%–95% (non‑condensing)
Vibration: IEC 60068‑2‑6 (5–200 Hz, 1 g)
Certifications: UL, CSA, CE, RoHS
4. Features
Screw Clamp Design: High clamping force, vibration‑proof; accepts single or double wires.
Broad Compatibility: Fits all Momentum discrete/analog bases and selected Quantum bases.
Tool‑Only Operation: Standard screwdriver (3.5 mm flathead); no special tools.
Modular & Snap‑On: Attaches firmly to I/O base; easy replacement.
Labelable: Front surface for marking I/O points.
Robust Construction: Industrial plastic resists chemicals, oils, and temperature extremes.
5. Applications
Field wiring for Modicon Momentum distributed I/O
Control panels, machine skids, process automation
Material handling, packaging, textile machinery
Retrofit of older 984/Quantum systems
High‑vibration industrial environments
6. Installation Instructions
Power Off: Disconnect all power to the I/O base.
Align Terminal Block: Match the 170XTS00100 to the base’s connector slots.
Snap Into Place: Press firmly until the block clicks and seats flush.
Prepare Wires: Strip 6–7 mm of insulation; use copper wire only.
Open Clamp: Turn screw counterclockwise to open the clamp.
Insert Wire: Fully insert stripped wire into terminal; avoid stray strands.
Tighten Screw: Torque to 0.5–0.6 N·m (4.5–5.5 in‑lb).
Verify: Gently tug wire to confirm secure clamping.
Label: Mark terminals per your wiring diagram.
7. Compatibility List
Momentum Discrete Bases: 170ADI/ADO/BDO series
Momentum Analog Bases: 170ANR series
Quantum Bases: 140XTS series (selected models)
Software: Unity Pro, Concept
8. Maintenance
Quarterly Inspection: Check for loose screws, discoloration, or cracked housing.
Torque Check: Retighten screws to specification if vibration is severe.
Cleaning: Use dry cloth only; avoid solvents.
Replacement: Replace if damaged or corroded.
9. Safety Instructions
Install and service only by qualified electrical personnel.
Always de‑energize the I/O base before wiring or replacing terminals.
Use copper wire only; do not mix wire sizes in one clamp.
Do not exceed rated voltage/current.
Keep terminals dry and free of conductive debris.
10. Troubleshooting
Loose Connection / Intermittent Signal
Retighten screw to correct torque.
Check wire insulation length and stripped condition.
Verify no wire strands are outside the clamp.
Cannot Insert Wire
Open screw fully (counterclockwise).
Check for bent or obstructed clamp.
Confirm wire gauge is within 1.5–2.5 mm².
Terminal Block Will Not Snap On
Align with base slots correctly.
Check for debris or damage on base connectors.