170NEF16021
Description
1. General Description
2. Product Identification
Model Number: 170NEF16021
Manufacturer: Schneider Electric (Modicon)
Product Line: Modicon Momentum (TSX Momentum)
Protocol: Modbus Plus (MB+), 984 data format
Network Type: Dual‑port (single‑cable or dual‑cable redundant)
Ports: 2 × shielded RJ45 (MB+ Port A / Port B)
Data Rate: Up to 1 Mbps
Power: 24 VDC (supplied via I/O base)
Power Consumption: ~2.4 W
Dimensions: 90 mm × 160 mm × 60 mm (W×H×D)
Weight: ~0.6 kg (1.3 lb)
Mounting: DIN rail (via I/O base)
Warranty: 18 months
Country of Origin: France
Status: Active (as of 2026)
3. Electrical & Environmental Specifications
Communication Interface: 2 × shielded RJ45 (MB+ pinout)
Signaling: RS485 differential, 1 Mbps, 984 format
Cable: Shielded twisted pair (MB+ compliant)
Max Network Length: 5,000 m (16,400 ft) with repeaters
Operating Voltage: 24 VDC ±10% (from I/O base)
Operating Temperature: -25 °C to +60 °C (-13 °F to 140 °F)
Storage Temperature: -40 °C to +85 °C (-40 °F to 185 °F)
Humidity: 5%–95% RH (non‑condensing)
Altitude: Up to 1,000 m (3,280 ft) (no derating)
Protection Class: IP20 (indoor use)
Certifications: UL, CSA, CE, RoHS
Compliance: California Prop 65 (lead warning)
EMI Immunity: 10 V/m (electromagnetic fields); 4 kV/8 kV ESD
4. Compatibility
Platforms: Modicon Momentum (170 series), Quantum, Premium
I/O Bases: All Momentum I/O bases (170 series)
PLCs: Modicon 984, Quantum, Premium, M340 (with MB+ interface)
Software: Unity Pro, MB+ Network Configurator, 984 Ladder Logic
Topologies: MB+ peer‑to‑peer, master‑slave, linear trunk/drop, redundant (dual‑cable)
5. Key Features
Dual‑Port MB+ (A/B): Supports standard or redundant MB+ networks (fault‑tolerant)
1 Mbps MB+ Speed: Deterministic, high‑speed data transfer
Dual RJ45 Ports: Daisy‑chain, star, or redundant topology support
Hot‑Swap Ready: Replace adapter without network shutdown
LED Status Indicators:
PWR (Green): Module powered up
MB+ ACT (Green): Network communication active
ERR A (Red): Network A communication error
ERR B (Red): Network B communication error
Shielded Connectors: EMI/RFI immunity for harsh environments
Easy Installation: Clips lock adapter to I/O base (no tools)
6. Applications
Distributed I/O in Momentum racks (MB+ network)
High‑speed PLC‑to‑I/O and PLC‑to‑PLC communication
Redundant MB+ networks (critical/high‑availability systems)
Factory floor automation (material handling, packaging, process control)
Retrofit of legacy 984 systems with modern Momentum I/O
Compact panel and machine‑mounted I/O solutions
7. Installation Instructions
Power Off: Disconnect power to the Momentum I/O base.
Align Adapter: Slide the 170NEF16021 onto the I/O base’s communication connector.
Lock in Place: Press until the side clips click, securing the adapter.
Connect MB+ Cables:
Standard Network: Plug shielded RJ45 cable into Port A.
Redundant Network: Plug cables into both Port A and Port B.
Terminate Network: Ensure 120 Ω termination resistors are installed at both ends of each MB+ trunk.
Power On: Restore power; verify PWR and MB+ ACT LEDs illuminate.
Configure Network: Use Unity Pro or MB+ Configurator to set the adapter’s unique MB+ address and enable redundancy (if required).
8. Maintenance
Quarterly Inspection: Check RJ45 connectors for wear, dirt, or bent pins.
LED Check: Verify PWR is on and MB+ ACT flashes during communication.
Cable Care: Avoid sharp bends, vibration, or stress on MB+ cables.
Shield Integrity: Ensure shield is grounded at one end only (MB+ standard).
Replacement: Replace adapter if ERR A/B is steady or communication fails (after cable/termination check).
9. Safety Precautions
Qualified Personnel: Installation/service by qualified technical staff only.
Power Disconnection: Always disconnect power before installing/removing the adapter.
Indoor Use Only: For indoor industrial environments; avoid moisture, direct sunlight.
Damage Check: Do not use if adapter, connectors, or insulation are damaged.
Disposal: Dispose per local electronic waste regulations.
10. Troubleshooting
No MB+ Communication (Port A or B)
Confirm PWR LED is on (24 VDC power to I/O base).
Check RJ45 cable is fully seated and locked.
Verify 120 Ω termination at trunk ends.
Ensure unique MB+ address (no duplicates).
Intermittent Communication
Inspect for loose RJ45 connectors or bent pins.
Check for excessive vibration or cable movement.
Verify shield is grounded at one end only.
Reduce network load or check for faulty nodes.
ERR A or ERR B (Red LED) On
MB+ network fault (short circuit, open cable, or duplicate address).
Check cable continuity and termination.
Verify no other node uses the same MB+ address.
In redundant mode, check both networks for faults.
Get a Quote