170MCI02080
Description
1. General Description
2. Product Identification
Model Number: 170MCI02080 (also 170‑MCI‑020‑80)
Manufacturer: Schneider Electric (Modicon)
Product Line: Modicon Momentum
Protocol: Modbus Plus (MB+) / RS485
Application: IP20 T‑junction, long‑haul inter‑rack links
Length: 10 m (≈30 ft)
Connectors: 2 × male RJ45 (shielded, MB+ pinout)
Cable Type: Shielded twisted pair (RS485 differential)
Weight: ~1 lb (0.45 kg)
Warranty: 18 months
Country of Origin: USA
Status: Active (as of 2026)
3. Electrical & Mechanical Specifications
Interface: RJ45 (shielded, MB+ pinout)
Wiring: Factory‑prewired, no field wiring
Shielding: 100% foil + braid (EMI/RFI protection)
Conductors: 2 twisted pairs (RS485 signaling)
Insulation: Industrial PVC (gray)
Bend Radius: ≥ 10× cable diameter
Operating Temperature: 0 °C to +60 °C
Storage Temperature: -40 °C to +85 °C
Humidity: 5%–95% (non‑condensing)
Protection Class: IP20
Certifications: CE, RoHS, UL, cUL, CSA; California Prop 65
4. Compatibility
Platforms: Modicon Momentum (170 series), Premium, Quantum
Devices: MB+ adapters (170MCIxxx), Momentum I/O bases with MB+
Topologies: MB+ trunk/drop, IP20 T‑junction, inter‑rack links
Software: Unity Pro, MB+ Network Configurator
5. Key Features
10 m length: Ideal for inter‑rack and long‑distance runs
Shielded RJ45: Industrial‑grade noise immunity
Plug‑and‑play: Pre‑tested, no wiring required
Hot‑swap compatible: Replace modules without network shutdown
MB+ 1 Mbps: Full deterministic performance at maximum length
Cluster‑mode ready: Connect multiple adapters across racks
6. Applications
Inter‑rack MB+ communication in large automation systems
IP20 T‑junction connections for extended MB+ networks
Remote I/O links between Momentum racks
High‑speed distributed I/O and peer‑to‑peer control
Factory floor and process control systems
7. Installation
Power off all connected devices.
Align RJ45 male connector with MB+ port on first module.
Insert firmly until latch clicks (ensures shield contact).
Repeat for second module’s MB+ port.
Verify both connectors are fully seated and locked.
Route cable with gentle bends; avoid sharp corners or crushing.
Power on system; verify MB+ network status in PLC software.
For T‑junction: Connect one end to trunk, other to drop module.
8. Maintenance
Inspect RJ45 connectors quarterly for wear, dirt, or bent pins.
Keep cable free of mechanical stress, sharp bends, or heavy loads.
Maintain shield integrity; follow MB+ grounding rules (single‑end ground).
Replace cable if insulation, shielding, or connectors are damaged.
9. Safety Notes
Installation/service only by qualified personnel.
Disconnect power before connecting/disconnecting the cable.
Indoor industrial use only; avoid direct sunlight, moisture, and chemicals.
Do not use if cable or connectors show damage.
Dispose of per local e‑waste regulations.
10. Troubleshooting
No MB+ communication:
Check both RJ45 connectors are fully latched.
Verify MB+ network power and termination (120 Ω at trunk ends).
Confirm unique MB+ addresses and correct network configuration.
Intermittent communication:
Inspect for loose latches, bent pins, or damaged shielding.
Check for excessive vibration or cable movement.
Verify proper shield grounding (single end only).
Get a Quote