170INT11000
Description
1. General Description
2. Product Identification
Model Number: 170INT11000
Series: Modicon Momentum
Type: Interbus Communication Adapter
Protocol: Interbus
Connector: 1 × 9-pin SUB-D interface
Transmission medium: Shielded twisted pair cable
Baud rate: Fixed 500 kbps
Station setting: Automatic address assignment
LED indicators: RUN, FLT status lamps
Dimensions: 125 × 45 × 100 mm
Weight: 0.08 kg
Protection Class: IP20
Certifications: CE, UL, cUL, CSA, RoHS
3. Communication Specifications
Network standard: Interbus fieldbus protocol
Transmission speed: 500 kbps fixed
Network topology: Ring topology
Maximum nodes per network: 512 stations
Maximum single segment distance: 400 meters
Data mode: Cyclic real-time exchange
Data verification: CRC check
Galvanic isolation between internal circuit and field bus
4. Electrical Specifications
Power supply: Powered by Momentum backplane 24 VDC
Operating voltage range: 19.2 VDC ~ 28.8 VDC
Typical current consumption: 105 mA
Built-in surge, electrostatic and overcurrent protection
Industrial EMC anti-interference performance
5. Environmental Ratings
Operating temperature: 0 °C to +60 °C, non-condensing
Storage temperature: -40 °C to +85 °C
Relative humidity: 5% ~ 95%, no condensation
Vibration test: Compliant with IEC 60068-2-6
Shock resistance: IEC 60068-2-27 standard
Maximum altitude: 5000 m, performance derating above 2000 m
6. Key Features
Standard Interbus fieldbus communication protocol
Stable 500 kbps real-time data transmission
Automatic station address recognition, no manual dial setting
Ring network structure improves system reliability
Plug-and-play installation on Momentum backplane
Dual LED diagnosis for quick fault location
Isolated design effectively suppresses field interference
No external auxiliary power required
7. Compatibility
Matching device: All Modicon Momentum I/O bases
Applicable controllers: Quantum, Premium, M340 series PLC
Configuration software: Unity Pro, SoMachine
Wiring cable: Interbus dedicated shielded twisted pair
Wiring specification: 14~22 AWG copper wire
8. Application Scope
Factory production line automatic control
Packaging, material handling and mechanical equipment
Industrial workshop distributed remote I/O collection
Water supply, drainage and HVAC automation system
Process monitoring and logic control projects
9. Installation & Operation
Cut off all power supply before installation work
Insert adapter into Momentum communication slot and lock firmly
Connect Interbus shielded cable to 9-pin SUB-D port
Complete ring network wiring according to site topology
Power on the system, observe RUN and FLT LED status
Finish network configuration and verify normal data communication
10. Maintenance
Inspect wiring tightness and LED status every half year
Keep module surface clean and dry without dust accumulation
Regularly check cable aging and shielding connection condition
Avoid long-term work in corrosive and strong vibration environment
11. Safety Notes
Installation and maintenance operated by qualified professional staff
Do not apply overvoltage to communication interface
Prohibit disassembly and damage internal isolation structure
Separate field bus cable from high voltage power cable
Scrap discarded module in accordance with local electronic waste rules
12. Troubleshooting
Fault LED alarm: Check ring wiring breakage and connection looseness
No data communication: Confirm backplane power and network master status
Abnormal data: Inspect cable shielding grounding and surrounding interference sources
System disconnection: Recheck ring loop integrity and terminal connection
Get a Quote