1. General Description
2. Product Identification
Model Number: 170BNO67100
Series: Modicon Momentum
Type: 8-channel relay discrete output module
Channel configuration: 8 relay outputs
Dimension: 125 × 47.5 × 141.5 mm
Weight: 0.29 kg
Protection Class: IP20
Certifications: CE, UL, cUL, CSA, RoHS
Isolation: 1780 VAC between field and internal circuit
LED indicators: 8 status LEDs for each output channel
3. Electrical Specifications
Relay Output
Contact type: Normally Open (NO)
Rated load voltage:
AC: 24 ~ 230 VAC
DC: 24 ~ 120 VDC
Continuous current per channel: 5 A resistive load
Inductive load current: 3 A @ 230 VAC
Max switching power: 1150 VA AC, 600 W DC
Minimum working load: 5 mA
Action response time: ≤ 10 ms
Mechanical service life: 10,000,000 cycles no load
Electrical service life: 100,000 cycles full resistive load
Power Supply
Logic supply: 24 VDC ±10%
Typical current consumption: 130 mA
Maximum power dissipation: 7 W
4. Environmental Ratings
Operating temperature: 0 °C to +60 °C, non-condensing
Storage temperature: -40 °C to +85 °C
Relative humidity: 5% ~ 95%, no condensation
Vibration: Compliant with IEC 60068-2-6
Shock resistance: IEC 60068-2-27
Max altitude: 5000 m, derate above 2000 m
EMC: Industrial level anti-interference performance
5. Key Features
8 isolated relay outputs for wide voltage load control
Heavy load capacity up to 5 A per channel
High galvanic isolation improves system safety
Detachable terminal blocks for easy wiring and replacement
Quick snap installation on Momentum backplane
Individual channel LED status indication
Suitable for frequent switching industrial actuators
6. Compatibility
Backplane: Modicon Momentum I/O rack
Matching adapters: 170ENT, 170PBM, 170CPS series
Applicable controllers: Quantum, Premium, M340, Momentum
Configuration software: Unity Pro, SoMachine
Wiring: 14~22 AWG copper wire, torque 0.5~0.6 N·m
7. Application Scope
Industrial motor, pump and fan switch control
Solenoid valve, contactor and actuator driving
230 VAC lighting and HVAC system control
Packaging, conveyor and mechanical equipment logic control
Water treatment and factory process on-site control
8. Installation & Wiring
Cut off all power supply before installation and wiring
Fasten the module onto Momentum base, complete reliable grounding
Connect AC/DC power and load to relay common and NO terminals
Install RC snubber for inductive loads to suppress surge voltage
Fasten terminal screws with standard torque value
Power on and verify LED channel working state
9. Daily Maintenance
Inspect terminal connection tightness every half year
Keep module surface clean and dry without dust accumulation
Regularly check relay contact abrasion and arc damage
Avoid corrosive gas, intense vibration and humid environment
10. Safety Instructions
Only professional electricians can perform wiring and maintenance work
Strictly follow rated voltage and current parameters
Do not damage internal isolation structure
External surge absorption device is required for inductive loads
Scrap module according to local electronic waste disposal rules