The 170ARM37030 is a discrete relay I/O base for the Schneider Electric Modicon Momentum distributed I/O platform. It provides 10 digital inputs and 8 relay outputs, designed for on/off control of actuators, motors, valves, and contactors in industrial automation. The module supports both AC and DC field signals, with high isolation for safety and noise immunity.

Description

1. General Description

The 170ARM37030 is a discrete relay I/O base for the Schneider Electric Modicon Momentum distributed I/O platform. It provides 10 digital inputs and 8 relay outputs, designed for on/off control of actuators, motors, valves, and contactors in industrial automation. The module supports both AC and DC field signals, with high isolation for safety and noise immunity.

2. Product Identification

  • Model Number: 170ARM37030

  • Series: Modicon Momentum

  • Type: Discrete relay I/O base (10I / 8O)

  • Channel Configuration:

    • 10 × discrete inputs (DI)

    • 8 × discrete relay outputs (DO, normally open)

  • Dimensions (W × D × H): 141.5 × 47.5 × 125 mm

  • Weight: 0.28 kg

  • Protection Class: IP20

  • Certifications: CE, UL, cUL, CSA, RoHS

  • Logic Type: Positive (true high) for inputs

  • Isolation:

    • Field ↔ Bus: 500 VAC, 1 minute

    • I/O Groups: 1780 VAC, 1 minute

  • LED Indicators: 10 green (DI), 8 red (DO), power/run status


3. Electrical Specifications

Discrete Inputs (10 Channels)

  • Signal Type: IEC 1131‑2 Type 1, positive logic

  • Voltage Range: 24 VDC nominal; −3 VDC to +30 VDC max

  • Logic 1: ≥ 11 VDC; Logic 0: ≤ 5 VDC

  • Input Current:

    • Logic 1: ≥ 2.5 mA

    • Logic 0: ≤ 1.2 mA

  • Response Time:

    • 0 → 1: < 2.2 ms

    • 1 → 0: < 3.3 ms

  • Input Resistance: ~4 kΩ

Discrete Relay Outputs (8 Channels, 2 Groups × 4)

  • Output Type: Relay, normally open (NO)

  • Voltage Rating: 24–230 VAC / 24–120 VDC

  • Current Rating (per channel):

    • Resistive load: 2 A @ 230 VAC / 24 VDC

    • Inductive load: 1 A @ 230 VAC (LR ≤ 40 ms)

  • Min. Load Current: 5 mA (for contact reliability)

  • Max. Switching Power: 500 VA (AC) / 240 W (DC)

  • Response Time:

    • On: < 10 ms

    • Off: < 5 ms

  • Mechanical Life: 10,000,000 operations (no load)

  • Electrical Life: 100,000 operations (full resistive load)

Power

  • Supply Voltage: 24 VDC ±10% (logic power)

  • Current Consumption: ≤ 250 mA @ 24 VDC

  • Power Dissipation: ≤ 8.5 W (max)


4. Environmental Ratings

  • Operating Temperature: 0 °C to +60 °C, non‑condensing

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 5% to 95%, non‑condensing

  • Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)

  • Shock: IEC 60068‑2‑27 (15 g, 11 ms)

  • Altitude: Up to 5000 m (derate above 2000 m)

  • EMC: IEC 61000‑6‑2 / 61000‑6‑4 (industrial)


5. Key Features

  • 10I / 8O Relay Mix: High‑count discrete I/O for machine and process control.

  • Wide Voltage Support: Inputs 24 VDC; outputs 24–230 VAC/DC.

  • High Isolation: 1780 VAC between I/O groups; 500 VAC field‑to‑bus.

  • Removable Terminal Blocks: Simplify wiring and hot‑swap replacement.

  • Snap‑On Mounting: Fast attachment to Momentum backplane.

  • LED Status: Per‑channel indication for quick diagnostics.

  • Obsolete Replacement: Replaced by 170ADM39030 (direct equivalent).


6. Compatibility

  • Backplane: Modicon Momentum I/O rack.

  • Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power).

  • PLC Compatibility: Quantum, Premium, M340, Momentum controllers.

  • Software: Unity Pro, SoMachine, Modbus RTU/TCP.

  • Terminals: 14–22 AWG copper wire, torque 0.5–0.6 N·m.


7. Applications

  • Machine Automation: Conveyors, packaging, material handling.

  • Process Control: Valve, motor, and contactor control.

  • Building Automation: HVAC, lighting, access control.

  • Water/Wastewater: Pump and actuator control.

  • Industrial Safety: Isolated on/off control for high‑voltage loads.


8. Installation & Wiring

  1. Power Off: Disconnect all system power before installation.

  2. Mounting: Snap module firmly onto Momentum backplane; ground the rack.

  3. Input Wiring (DI1–DI10):

    • Connect 24 VDC sensor output to DI terminal; common to 24 VDC GND.

  4. Output Wiring (DO1–DO8, NO):

    • Connect load between DO terminal and AC/DC supply (24–230 V).

  5. Torque: Tighten terminals to 0.5–0.6 N·m.

  6. Verification: Power on; confirm LED status (DI = green, DO = red).


9. Maintenance

  • Periodic Inspection: Check terminal tightness and LED operation every 6 months.

  • Cleaning: Use dry cloth only; avoid moisture and chemicals.

  • Relay Contact Check: Test under load annually; replace if arcing or high resistance.

  • Environment: Avoid corrosive gases, heavy vibration, and condensation.


10. Safety Notes

  • Qualified Personnel: Only certified electricians may perform wiring/maintenance.

  • Voltage Limits: Do not exceed 30 VDC on inputs; 230 VAC on outputs.

  • Current Ratings: Adhere to 2 A resistive / 1 A inductive per channel.

  • Isolation Integrity: Do not defeat isolation barriers; maintain 500 VAC field‑to‑bus.

  • Relay Arcing: Inductive loads require suppression (RC snubber or varistor).

  • Disposal: Dispose of module per local e‑waste regulations.