1. General Description
2. Product Identification
Model: 170ANR12090
Series: Modicon Momentum
Type: 8-channel single-ended analog input module
Channel quantity: 8 analog inputs
Dimension: 125 × 47.5 × 141.5 mm
Weight: 0.23 kg
Protection class: IP20
Certification: CE, UL, cUL, CSA, RoHS
Isolation: 500 VAC between field and bus
Indicator: Power and channel status LED
3. Electrical Specifications
Analog Input
Resolution: 12 bit
Selectable input signal range:
4~20 mA, 0~20 mA, 1~5 V, 0~10 V
Input impedance
Current mode: 250 Ω
Voltage mode: > 1 MΩ
Basic accuracy: ±0.1 % full scale
Temperature drift: ±0.005 % FS / °C
Conversion time: 4 ms per channel
Built-in noise filter, software configurable
Power Supply
Supply voltage: 24 VDC ±10%
Power consumption: 180 mA typical
Max power dissipation: 3.5 W
4. Environmental Specifications
Operating temperature: 0 °C ~ +60 °C, non-condensing
Storage temperature: -40 °C ~ +85 °C
Relative humidity: 5% ~ 95%, no condensation
Vibration resistance: IEC 60068-2-6
Altitude: Max 5000 m, power derating above 2000 m
EMC compliance: Industrial standard immunity
5. Key Features
8 universal analog input channels, flexible range selection
12-bit high precision signal conversion
Removable terminal block for easy wiring and replacement
Snap-on installation for Momentum backplane
Built-in surge and overvoltage protection
Isolated design improves anti-interference capability
Real-time LED status diagnosis
6. Compatibility
Backplane: Momentum I/O rack
Communication adapters: 170ENT, 170PBM, 170CPS series
Compatible PLC: Quantum, Premium, M340, Momentum controller
Configuration software: Unity Pro, SoMachine
Wire specification: 14~22 AWG copper wire, torque 0.5~0.6 N·m
7. Application
Process parameter monitoring: pressure, flow, liquid level, temperature
Industrial factory automation
Water treatment and energy monitoring system
HVAC and building automatic control
Material handling and packaging machine
8. Installation & Wiring
Cut off all power before installation
Clip module firmly onto Momentum base rack and ground properly
Current signal: Connect transmitter two wires to analog input terminals
Voltage signal: Connect sensor output to corresponding channel terminals
Use shielded twisted pair cable for analog wiring
Tighten terminal screws with standard torque
Power on and check LED working status
9. Maintenance
Inspect terminal tightness and LED status every 6 months
Keep module surface clean and dust-free
Avoid corrosive gas, heavy vibration and damp environment
Regular check cable shielding connection
10. Safety Notes
Only qualified personnel perform wiring and maintenance
Do not exceed rated input voltage and current range
Keep isolation integrity between field side and control bus
Separate analog cable from high power cable to avoid interference
Dispose module according to local electronic waste regulation