170AMM09000
Description
1. General Description
2. Product Identification
Model Number: 170AMM09000
Series: Modicon Momentum
Type: Mixed analog/discrete I/O base
Channel Configuration:
4 × analog differential inputs (AI)
2 × analog outputs (AO)
4 × discrete inputs (DI)
2 × discrete outputs (DO)
Dimensions (W × D × H): 141.5 × 47.5 × 125 mm
Weight: 0.24 kg
Protection Class: IP20
Certifications: CE, UL, cUL, CSA, FM Class 1 Division 2, RoHS
Logic Type: Positive (true high) for discrete I/O
Isolation:
Field ↔ Bus: 1500 VAC, 1 minute
Analog ↔ Discrete: 500 VAC, 1 minute
LED Indicators: 4 green (DI), 2 yellow (DO), status LEDs for AI/AO
3. Electrical Specifications
Discrete Inputs (4 Channels, 24 VDC)
Voltage Range: −3 VDC to +30 VDC (24 VDC nominal)
Logic 1: ≥ 11 VDC; Logic 0: ≤ 5 VDC
Input Current: 8 mA @ 24 VDC
Response Time:
0 → 1: < 2.2 ms
1 → 0: < 3.3 ms
Status 0 Current: ≤ 1.2 mA; Status 1 Current: ≥ 2.5 mA
Discrete Outputs (2 Channels, 24 VDC, Sourcing)
Output Type: Transistor (sourcing, positive logic)
Rated Voltage: 24 VDC ±20%
Current Rating:
Per channel: 1 A (continuous)
Per group/module: 2 A
Voltage Drop (On): < 0.5 V @ 1 A
Leakage Current (Off): ≤ 1 mA @ 24 VDC
Response Time: < 0.1 ms (both directions)
Protection: Electronic short‑circuit & overload (auto‑reset)
Analog Inputs (4 Differential Channels, 12‑Bit)
Input Ranges (Software Selectable):
Voltage: ±10 V, ±5 V, 1–5 V
Current: ±20 mA, 4–20 mA
Resolution: 12 bits (0.025% FS)
Accuracy: ±0.03% FS @ 25 °C; ±0.003%/°C drift
Input Impedance:
Voltage: > 1 MΩ
Current: 250 Ω
Filter: Programmable (0–100 ms)
Fail State: Hold last value
Analog Outputs (2 Channels, 12‑Bit)
Output Ranges (Software Selectable):
Voltage: ±10 V
Current: 0–20 mA, 4–20 mA
Resolution: 12 bits
Accuracy: ±0.05% FS @ 25 °C
Load Limits:
Voltage: ≥ 3 kΩ
Current: ≤ 600 Ω
Response Time: < 5 ms (0–100% step)
Fail State: Reset to zero (configurable)
Power
Supply Voltage: 24 VDC ±20% (logic + field)
Current Consumption: ≤ 350 mA @ 24 VDC (full load)
Power Dissipation: 4 W typical, 6 W maximum
4. Environmental Ratings
Operating Temperature: 0 °C to +60 °C, non‑condensing
Storage Temperature: −40 °C to +85 °C, non‑condensing
Relative Humidity: 5% to 95%, non‑condensing
Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)
Shock: IEC 60068‑2‑27 (15 g, 11 ms)
Altitude: Up to 5000 m (derate above 2000 m)
EMC: IEC 61000‑6‑2, IEC 61000‑6‑4 (industrial immunity)
5. Key Features
Mixed I/O Integration: 4AI/2AO/4DI/2DO in one module, reducing system cost.
Differential Analog Inputs: High noise rejection for precise measurement in industrial environments.
Software‑Configurable Ranges: Analog I/O ranges selectable via Unity Pro/SoMachine.
12‑Bit Precision: Accurate analog measurement and control.
Removable Terminal Blocks: Simplify wiring and module replacement.
Snap‑On Mounting: Fast attachment to Momentum backplane.
LED Status: Real‑time indication of discrete I/O state.
High Isolation: 1500 VAC field‑to‑bus isolation for safety.
6. Compatibility
Backplane: Modicon Momentum I/O base rack.
Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power supply).
PLC Compatibility: Quantum, Premium, M340, Momentum controllers.
Software: Unity Pro, SoMachine, Modbus protocol.
Terminals: 14–22 AWG copper wire, torque 0.5–0.6 N·m.
7. Applications
Process Control: Temperature, pressure, flow, level monitoring/control.
Infrastructure & Energy: Power monitoring, HVAC, water/wastewater.
Material Handling: Conveyor speed control, load cell measurement.
Machine Automation: Analog sensor input + digital actuator output.
Building Automation: Environmental monitoring, lighting, and HVAC control.
8. Installation & Wiring
Power Off: Disconnect all system power before installation.
Mounting: Snap module firmly onto Momentum backplane; ensure proper grounding.
Wiring – Discrete Inputs (DI1–DI4):
Connect 24 VDC sensor output to DI terminal; common to 24 VDC ground.
Wiring – Discrete Outputs (DO1–DO2):
Connect load between DO terminal and 24 VDC positive.
Wiring – Analog Inputs (AI1–AI4, Differential):
Connect signal + to AI+, signal − to AI−; shield to ground.
Wiring – Analog Outputs (AO1–AO2):
Connect load across AO+ and AO−; shield to ground.
Torque: Tighten terminals to 0.5–0.6 N·m (14–22 AWG copper wire).
Verification: Check connections; power on and confirm LED status.
9. Maintenance
Periodic Inspection: Check terminal tightness and LED operation every 6 months.
Cleaning: Keep surface free of dust and contaminants; use dry cloth only.
Environment: Avoid corrosive gases, extreme vibration, or moisture.
Firmware: Update via Unity Pro for latest features and bug fixes.
10. Safety Notes
24 VDC Hazard: Only qualified electricians should perform wiring; follow local codes.
Voltage Limits: Do not exceed 30 VDC on discrete inputs / 28.8 VDC on outputs.
Current Ratings: Adhere to 1 A per DO channel / 2 A per module limits.
Isolation: Maintain 1500 VAC field‑to‑bus and 500 VAC analog‑discrete isolation.
Analog Wiring: Use shielded twisted‑pair cable for analog signals; separate from high‑voltage cables.
Disposal: Dispose of module per local electronic waste regulations.
Get a Quote