170ADM69051
Description
1. General Description
2. Product Identification
Model Number: 170ADM69051
Series: Modicon Momentum
Type: Discrete AC I/O base (solid‑state TRIAC outputs, high‑noise immunity)
Channel Configuration:
10 inputs (120 VAC, 47–63 Hz, positive logic)
8 outputs (120 VAC, TRIAC, 2 groups of 4)
Dimensions (W × D × H): 125 × 47.5 × 141.5 mm
Weight: 0.25 kg
Protection Class: IP20
Certifications: CE, UL, cUL, CSA, RoHS, Green Premium
Logic Type: Positive (true high)
Isolation (Field ↔ Bus): 1780 VAC
Key Difference (vs 170ADM69050): Enhanced EMI filtering, upgraded surge suppression, improved noise immunity for harsh environments.
3. Electrical Specifications
Inputs (10 Channels, 120 VAC)
Rated Voltage: 120 VAC (74–132 VAC operating range)
Frequency: 47–63 Hz
Logic 0 (Low): ≤ 20 VAC
Logic 1 (High): ≥ 74 VAC
Input Current (High): ≥ 5.5 mA
Input Resistance: 4 kΩ
Response Time:
0 → 1: ≤ 12.5 ms @ 60 Hz
1 → 0: ≤ 12.3 ms @ 60 Hz
Surge Withstand: 200 VAC (transient), enhanced ESD filtering.
Outputs (8 Channels, TRIAC, 120 VAC)
Rated Voltage: 120 VAC (108–132 VAC, 47–63 Hz)
Output Type: Isolated TRIAC, non‑zero crossing, high‑noise immunity.
Current Rating:
Per channel: 0.5 A (continuous)
Per group (4 channels): 2 A
Per module (8 channels): 4 A
Leakage Current (Off): ≤ 1.3 mA @ 120 VAC
Voltage Drop (On): ≤ 1.5 V @ 0.5 A
Response Time:
0 → 1: ≤ 12.5 ms @ 60 Hz
1 → 0: ≤ 12.3 ms @ 60 Hz
Protection: Per‑channel overload/short‑circuit protection with LED fault indication; enhanced inductive load surge suppression.
Power
Supply Voltage: 120 VAC ±10% (96–138 VAC, 47–63 Hz)
Current Consumption: 160 mA @ 120 VAC
Power Dissipation: ≤ 6 W (max)
4. Environmental Ratings
Operating Temperature: 0 °C to +60 °C (32 °F to 140 °F), non‑condensing
Storage Temperature: −40 °C to +85 °C, non‑condensing
Relative Humidity: 5% to 95%, non‑condensing
Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)
Shock: IEC 60068‑2‑27 (15 g, 11 ms)
Altitude: Up to 5000 m (derate above 2000 m)
EMC: IEC 61000‑6‑2, IEC 61000‑6‑4 (enhanced noise immunity)
5. Key Features
18 LED Indicators: 10 for input status, 8 for output status (green = on, red = fault).
120 VAC Native I/O: Eliminates need for AC/DC converters in 120 VAC panels.
TRIAC Outputs: Solid‑state, no mechanical wear, ideal for high‑cycle loads.
Removable Terminal Blocks: Simplify wiring and module replacement.
Snap‑On Mounting: Fast attachment to Momentum backplane.
Grouped Outputs: 2×4 TRIACs for independent load grouping.
Per‑Channel Protection: Overload/short‑circuit protection with LED fault indication.
Galvanic Isolation: 1780 VAC isolation between field and bus circuits.
High‑Noise Immunity: Enhanced filtering for operation in MCC cabinets, near high‑frequency motors, and contactor banks.
6. Compatibility
Backplane: Modicon Momentum I/O base rack.
Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power supply) series.
PLC Compatibility: Quantum, Premium, M340, Momentum controllers.
7. Applications
120 VAC Sensors: Limit switches, pushbuttons, proximity sensors.
AC Actuators: Solenoids, contactors, relays, small motors (≤ 0.5 A).
Building Automation: Lighting, HVAC, fan control (120 VAC).
Industrial Control: Conveyors, pumps, heaters, low‑voltage switchgear.
High‑Cycle Loads: TRIACs ideal for frequent switching (no mechanical contacts).
Harsh Environments: Optimized for high‑electrical‑noise areas (MCC rooms, motor control centers).
8. Installation & Wiring
Power Off: Disconnect all system power before installation.
Mounting: Snap module firmly onto Momentum backplane; ensure proper grounding.
Wiring (Inputs – 120 VAC):
Connect 120 VAC line to input terminal; neutral to common (COM) terminal.
Wiring (Outputs – TRIAC):
Each TRIAC has OUT and COM terminals.
Connect load between OUT and COM; route 120 VAC line to COM, neutral to load.
For inductive loads: Install external RC snubber to suppress voltage spikes.
Torque: Tighten terminals to 0.5–0.6 N·m (14–22 AWG copper wire).
Verification: Check connections; power on and confirm LED status (green = active).
9. Maintenance
Periodic Inspection: Check terminal tightness and LED operation every 6 months.
Cleaning: Keep surface free of dust and contaminants; use dry cloth only.
Environment: Avoid corrosive gases, extreme vibration, or moisture.
Output Check: For high‑cycle applications, verify TRIAC leakage current annually.
10. Safety Notes
120 VAC Hazard: Only qualified electricians should perform wiring; follow local electrical codes.
Voltage Limits: Do not exceed 132 VAC on inputs/outputs.
Current Ratings: Adhere to 0.5 A per channel / 4 A per module limits.
Isolation: Maintain 1780 VAC isolation between field and bus circuits.
Inductive Loads: Always use external RC snubbers to protect TRIAC outputs.
Disposal: Dispose of module per local electronic waste regulations.
Get a Quote