170ADM39010
May 23, 2026

170ADM39010

The 170ADM39010 is a 24 VDC discrete input/output (I/O) base for the Schneider Electric Modicon Momentum distributed I/O platform. It provides 16 monitored digital inputs and 12 diagnostic solid‑state outputs in a compact IP20 housing, designed for direct connection to 24 VDC field devices and Momentum backplane adapters. This module features built‑in input monitoring and output diagnostics for enhanced fault detection in industrial automation systems.

Description

1. General Description

The 170ADM39010 is a 24 VDC discrete input/output (I/O) base for the Schneider Electric Modicon Momentum distributed I/O platform. It provides 16 monitored digital inputs and 12 diagnostic solid‑state outputs in a compact IP20 housing, designed for direct connection to 24 VDC field devices and Momentum backplane adapters. This module features built‑in input monitoring and output diagnostics for enhanced fault detection in industrial automation systems.

2. Product Identification

  • Model Number: 170ADM39010

  • Series: Modicon Momentum

  • Type: Discrete solid‑state I/O base (DC)

  • Channel Configuration:

    • 16 monitored inputs (sinking, positive logic)

    • 12 diagnostic outputs (sourcing, solid‑state)

  • Dimensions (W × D × H): 125 × 47.5 × 141.5 mm

  • Weight: 0.23 kg

  • Protection Class: IP20

  • Certifications: CE, UL, cUL, CSA, RoHS, Green Premium

  • Logic Type: Positive (true high)

  • Input Standard: IEC 61131‑2 Type 1


3. Electrical Specifications

Inputs (16 Channels, Monitored, Sinking)

  • Rated Voltage: 24 VDC (−3 VDC to +30 VDC range)

  • Logic 0 (Low): −3 VDC to 5 VDC

  • Logic 1 (High): 11 VDC to 30 VDC

  • Input Current (High): ≥ 2.5 mA

  • Input Resistance: 4 kΩ

  • Response Time:

    • 0 → 1: ≤ 2.2 ms

    • 1 → 0: ≤ 3.3 ms

  • Monitoring: Per‑channel open/short‑circuit detection

Outputs (12 Channels, Diagnostic, Sourcing, Solid‑State)

  • Rated Voltage: 24 VDC (≤ 30 VDC max)

  • Output Type: Sourcing (positive switching) solid‑state switch

  • Current per Point: 0.5 A (continuous)

  • Current per Module: 8 A (max)

  • Peak Current: 5 A (per point, short duration)

  • Leakage Current (Off): < 1 mA @ 24 VDC

  • Voltage Drop (On): < 0.5 V @ 0.5 A

  • Response Time: ≤ 0.1 ms (both directions)

  • Protection: Overload, short‑circuit (per channel)

  • Diagnostics: Per‑channel overcurrent, open‑load detection

Power

  • Supply Voltage: 24 VDC ±10% (19–30 VDC)

  • Current Consumption: 250 mA @ 24 VDC

  • Power Dissipation: 6.5 W (typical), ≤ 10 W (max)

  • Isolation (Channels ↔ Bus): 500 VAC


4. Environmental Ratings

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −25 °C to +85 °C

  • Relative Humidity: 5% to 95% (non‑condensing)

  • Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)

  • Altitude: Up to 5000 m (derate above 2000 m)


5. Key Features

  • 28 LED Indicators: 16 for input status, 12 for output status, plus error LEDs

  • Input Monitoring: Detects open/short circuits on each input channel

  • Output Diagnostics: Identifies overcurrent or open‑load conditions per output

  • Solid‑State Outputs: No moving parts; long life, high speed

  • Removable Terminal Blocks: Simplifies wiring and maintenance

  • Snap‑On Mounting: Quick attachment to Momentum backplane

  • Per‑Channel Protection: Overload/short‑circuit protection with LED fault indication


6. Compatibility

  • Backplane: Modicon Momentum I/O base rack

  • Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power supply) series

  • PLC Compatibility: Quantum, Premium, M340, Momentum controllers


7. Applications

  • 24 VDC sensors (proximity, photo‑eye, limit switches) requiring fault monitoring

  • Solenoids, contactors, relays, and small DC motors needing diagnostic feedback

  • Factory automation, material handling, packaging machinery

  • Process control systems requiring high reliability and fault detection


8. Installation & Wiring

  1. Power Off: Disconnect all system power before installation.

  2. Mounting: Snap module firmly onto Momentum backplane; ensure proper grounding.

  3. Wiring (Inputs – Sinking):

    • Connect +24 VDC from field device to input terminal; common (COM) to ground.

  4. Wiring (Outputs – Sourcing):

    • Connect load between output terminal and ground (0 VDC).

    • For inductive loads: Install flyback diode across load to absorb voltage spikes.

  5. Torque: Tighten terminals to 0.5–0.6 N·m (14–22 AWG copper wire).

  6. Verification: Check connections; power on and confirm LED status and diagnostics.


9. Maintenance

  • Periodic Inspection: Check terminal tightness and LED operation every 6 months.

  • Cleaning: Keep surface free of dust and contaminants.

  • Environment: Avoid corrosive gases, extreme vibration, or moisture.


10. Safety Notes

  • Monitored Inputs: Verify sensor wiring to avoid false fault triggers.

  • Diagnostic Outputs: Use appropriate load types to ensure accurate fault detection.

  • Inductive Loads: Always use external suppression (diodes/snubbers) to protect outputs.

  • Qualified Personnel: Only trained electricians should perform wiring; follow local codes.

  • Disposal: Dispose of module per local electronic waste regulations.


Get a Quote