170ADM35011
May 23, 2026

170ADM35011

The 170ADM35011 is a high‑speed 24 VDC discrete input/output (I/O) base for the Schneider Electric Modicon Momentum distributed I/O system. It provides 16 digital inputs and 16 solid‑state outputs in a compact IP20 housing, optimized for fast response and direct connection to 24 VDC field devices and Momentum backplane adapters.

Description

1. General Description

The 170ADM35011 is a high‑speed 24 VDC discrete input/output (I/O) base for the Schneider Electric Modicon Momentum distributed I/O system. It provides 16 digital inputs and 16 solid‑state outputs in a compact IP20 housing, optimized for fast response and direct connection to 24 VDC field devices and Momentum backplane adapters.

2. Product Identification

  • Model Number: 170ADM35011

  • Series: Modicon Momentum

  • Type: High‑Speed Discrete Solid‑State I/O Base (DC)

  • Channel Configuration:

    • 1 group of 16 inputs

    • 2 groups of 8 outputs (16 total)

  • Dimensions (W × D × H): 125 × 47.5 × 141.5 mm

  • Weight: 0.2 kg

  • Protection Class: IP20

  • Certifications: CE, UL, cUL, CSA, RoHS, Green Premium

  • Logic Type: Positive (sink) logic

  • Input Standard: IEC 61131‑2 Type 1


3. Electrical Specifications

Inputs (16 Channels)

  • Rated Voltage: 24 VDC (−3 VDC to +30 VDC range)

  • Logic 0 (Low): −3 VDC to 5 VDC

  • Logic 1 (High): 11 VDC to 30 VDC

  • Input Current (High): ≈12 mA

  • Input Resistance: 4 kΩ

  • Response Time: 0.06 ms (typical, high‑speed)

Outputs (16 Channels, Solid‑State)

  • Rated Voltage: 24 VDC (≤30 VDC max)

  • Output Type: Sink (negative switching) solid‑state switch

  • Current per Point: 0.5 A (continuous)

  • Current per Group: 4 A (max)

  • Current per Module: 8 A (max)

  • Peak Current: 5 A (per point, short duration)

  • Leakage Current (Off): <1 mA @ 24 VDC

  • Voltage Drop (On): <0.5 V @ 0.5 A

  • Response Time: ≤0.1 ms (0→1); ≤2 ms (1→0)

  • Protection: Overload, short‑circuit (per group)

Power

  • Supply Voltage: 24 VDC ±10%

  • Current Consumption: 250 mA @ 24 VDC

  • Power Dissipation: ≤8 W

  • Isolation (Channels ↔ Bus): 500 VAC


4. Environmental Ratings

  • Operating Temperature: 0 °C to +60 °C

  • Storage Temperature: −40 °C to +85 °C

  • Relative Humidity: 5% to 95% (non‑condensing)

  • Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)

  • Altitude: Up to 5000 m (derate above 2000 m)


5. Key Features

  • 32 LED Indicators: 16 for input status, 16 for output status

  • High‑Speed I/O: 0.06 ms input / 0.1 ms output response

  • Solid‑State Outputs: No moving parts; long life, high speed

  • Removable Terminal Blocks: Simplifies wiring and maintenance

  • Snap‑On Mounting: Quick attachment to Momentum backplane

  • Grouped Outputs: 2 × 8 channels for fault isolation and current sharing

  • Overload/Short‑Circuit Protection: Per group; automatic shutdown + LED fault indication

  • Green Premium: RoHS compliant, environmental transparency


6. Compatibility

  • Backplane: Modicon Momentum I/O base rack

  • Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power supply) series

  • PLC Compatibility: Quantum, Premium, M340, Momentum controllers


7. Applications

  • High‑speed 24 VDC sensors (proximity, photo‑eye)

  • Fast‑acting solenoids, contactors, and small DC motors

  • Factory automation, material handling, packaging machinery

  • Infrastructure and energy systems requiring rapid I/O response


8. Installation & Wiring

  1. Power Off: Disconnect all system power before installation.

  2. Mounting: Snap module firmly onto Momentum backplane; ensure proper grounding.

  3. Wiring (Inputs):

    • Connect 24 VDC field signals to input terminals; common (COM) per 8 inputs.

  4. Wiring (Outputs):

    • Sink outputs: Connect load between positive (+24 VDC) and output terminal.

    • For inductive loads: Install flyback diode across load to absorb voltage spikes.

  5. Torque: Tighten terminals to 0.5–0.6 N·m (14–22 AWG copper wire).

  6. Verification: Check connections; power on and confirm LED status.


9. Maintenance

  • Periodic Inspection: Check terminal tightness and LED operation every 6 months.

  • Cleaning: Keep surface free of dust and contaminants.

  • Environment: Avoid corrosive gases, extreme vibration, or moisture.


10. Safety Notes

  • High Speed: Solid‑state outputs switch rapidly; do not exceed load ratings.

  • Inductive Loads: Use external suppression (diodes/snubbers) to protect outputs.

  • Qualified Personnel: Only trained electricians should perform wiring; follow local codes.

  • Disposal: Dispose of module per local electronic waste regulations.


Get a Quote