170ADI54050
Description
1. General Description
2. Product Identification
Model Number: 170ADI54050
Series: Modicon Momentum
Type: AC Discrete Input Base
Channel Configuration: 16 inputs (2 × 8)
Dimensions (W × D × H): 125 × 47.5 × 141.5 mm
Weight: 0.284 kg
Protection Class: IP20
Certifications: CE, UL, cUL, CSA, FM Class 1 Div 2, RoHS
Logic Type: Positive logic (IEC 61131‑2 Type 2)
3. Electrical Specifications
Rated Input Voltage: 100–120 VAC, 50/60 Hz
Logic Low (0): ≤ 20 VAC
Logic High (1): ≥ 70 VAC
Typical Input Current: 10 mA per channel @ 120 VAC
Max Power Consumption: ≤ 125 mA @ 120 VAC
Response Time: 15 ms (typical)
Isolation Voltage: 1780 VAC (between channels, groups, and backplane)
Input Leakage Current: ≤ 1 mA (off state)
4. Environmental Ratings
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −25 °C to +85 °C
Relative Humidity: 5% to 95% (non‑condensing)
Vibration: IEC 60068‑2‑6 (1 g, 10–150 Hz)
Altitude: Up to 5000 m (derate above 2000 m)
5. Features
16 LED Indicators: One per channel for real‑time status (ON/OFF)
High Isolation: 1780 VAC reinforced isolation for noise immunity
Removable Terminal Blocks: Tool‑friendly wiring and maintenance
Snap‑On Mounting: Quick attachment to Momentum backplane (DIN rail or panel mount)
Grouped Inputs: 2 × 8 channels for flexible wiring and fault isolation
6. Compatibility
Backplane: Modicon Momentum I/O base rack
Adapters: 170ENT (Ethernet), 170PBM (Profibus), 170CPS (power supply) series
PLC Compatibility: Quantum, Premium, M340, and Momentum controllers
7. Applications
120 VAC pushbuttons, selector switches, and limit switches
AC relay contacts and motor control interlocks
North American standard industrial panels and machinery
Energy, infrastructure, material handling, and factory automation
8. Installation & Wiring
Power Off: Disconnect all system power before installation.
Mounting: Snap the module firmly onto the Momentum backplane. Ensure proper grounding.
Wiring:
Connect 100–120 VAC field signals to the corresponding input terminals.
Common terminals (COM) are grouped per 8 channels.
Use copper conductors (14–22 AWG). Torque terminals to 0.5–0.6 N·m.
Verification: Check all connections; power on the system and verify LED status.
9. Maintenance
Periodic Inspection: Check terminal tightness and LED operation every 6 months.
Cleaning: Keep the module surface free of dust and contaminants.
Environment: Avoid exposure to corrosive gases, extreme vibration, or direct moisture.
10. Safety Notes
Isolation: The 1780 VAC isolation does not protect against direct contact with high voltage.
Wiring: Only qualified personnel should perform wiring. Follow local electrical codes.
Disposal: Dispose of the module in accordance with local electronic waste regulations.
Get a Quote