170ADI34000
May 23, 2026

170ADI34000

170ADI34000 is a 16-channel 24VDC digital input module for Momentum distributed I/O system. It acquires switching signals from field sensors and sends data to PLC controller.

Description

1. General Description

170ADI34000 is a 16‑channel 24 VDC discrete input base for the Modicon Momentum distributed I/O system. It collects on/off signals from field sensors and switches and transmits them to the PLC.

2. Product Identification

  • Model: 170ADI34000

  • Series: Modicon Momentum

  • Type: Discrete Input Base (DC)

  • Channels: 16 inputs (1 group)

  • Weight: 0.19 kg

  • Dimensions: 125 mm × 47.5 mm × 141.5 mm

  • Protection: IP20

  • Certifications: CE, UL, cUL, FM Class 1 Div 2, RoHS

  • Status: Active

3. Electrical Specifications

  • Input voltage: 24 VDC (−3 V to +30 V range)

  • Input logic: Positive (sink/source compatible)

  • IEC 61131‑2 Type 1 compliant

  • “0” state: −3 V to +5 V, ≤1.2 mA

  • “1” state: +11 V to +30 V, ≥2.5 mA

  • Input resistance: 4 kΩ

  • Response time:

    • OFF → ON: 2.2 ms

    • ON → OFF: 3.3 ms

  • Current draw: ≤250 mA @ 24 VDC

  • Isolation: Field‑to‑adapter 500 VAC

4. Environmental Rating

  • Operating temp: 0 °C to +60 °C

  • Storage temp: −25 °C to +85 °C

  • Relative humidity: 5%–95%, non‑condensing

  • Vibration: IEC 60068‑2‑6 compliant

5. Main Features

  • 16 self‑diagnosing discrete inputs

  • 16 front‑panel LEDs for channel status

  • Compact, snap‑on DIN rail or panel mount

  • Plug‑in terminal strips for fast wiring

  • Compatible with standard Momentum adapters

6. Compatibility

  • Momentum base unit mounting

  • Communication adapters: 170ENT, 170PBM, 170CPS series

  • PLC compatibility: Quantum, Premium, M340

7. Application

  • Limit switches, proximity sensors, pushbuttons

  • Relay contact monitoring

  • Safety interlock and door status inputs

  • General machine I/O and factory automation

8. Installation & Wiring

  1. Power off the system.

  2. Snap module onto DIN rail or panel‑mount.

  3. Connect 24 VDC and sensor/common lines.

  4. Torque terminals to spec.

  5. Verify LED status before restoring power

9. Maintenance

  • Inspect terminals annually for tightness.

  • Keep front‑panel LEDs clear for status visibility.

  • Avoid corrosive atmospheres and excessive vibration