170AAI03000 is an 8-channel analog input module for Modicon Momentum distributed I/O system. It converts field analog signals into digital data for PLC processing, widely used for sensor signal collection in industrial automation.

Description

1. General Description

170AAI03000 is an 8-channel analog input module for Modicon Momentum distributed I/O system. It converts field analog signals into digital data for PLC processing, widely used for sensor signal collection in industrial automation.

2. Product Identification

  • Model: 170AAI03000

  • Series: Modicon Momentum

  • Type: Analog Input Module

  • Channel quantity: 8 isolated channels

  • Net weight: 0.18 kg

  • Protection class: IP20

  • Certifications: CE, UL, cUL, RoHS

  • Operating status: Active

3. Electrical Specifications

  • Input signal type: 4~20mA current signal

  • Input resistance: 125 Ω

  • Resolution: 15 bits

  • Conversion speed: 4 ms per channel

  • Isolation: Galvanic isolation between channels and backplane

  • Rated voltage: 300 V

  • Power supply: Powered by Momentum base unit

4. Environmental Rating

  • Operating temperature: 0 °C to +60 °C

  • Storage temperature: -25 °C to +85 °C

  • Relative humidity: 5%~95%, non-condensing

  • Vibration resistance: Compliant with IEC 60068-2-6

5. Main Features

  • Isolated design enhances anti-interference performance

  • Supports standard industrial current transmitter signal

  • Compact structure, easy installation and maintenance

  • Diagnostics function for circuit fault detection

  • Compatible with multiple Momentum communication adapters

6. Compatibility

  • Matching base unit: 170ADO, 170ADI series base

  • Communication adapters: 170ENT, 170CPS, 170PBM series

  • Applicable controller: Modicon Quantum, Premium, M340 PLC

7. Application

  • Pressure, flow, temperature transmitter signal acquisition

  • Industrial process parameter monitoring

  • Factory workshop distributed analog signal collection

8. Installation & Wiring

  1. Power off the whole system before assembly

  2. Snap the module onto Momentum base unit firmly

  3. Strip wire and connect 4~20mA sensor cable to corresponding terminal

  4. Tighten terminal screws with standard torque

  5. Check wiring integrity then restore power supply

9. Maintenance

  • Regularly check terminal connection tightness

  • Keep module surface clean and dust-free

  • Avoid strong electromagnetic field and corrosive gas environment