140XTS00200
Description
Type: I/O terminal block, 40 points, screw connection
Function: Field wiring termination for Quantum I/O modules
Net weight: Approximately 0.18 kg (0.40 lb)
Housing material: UL94 V‑0 flame‑retardant thermoplastic
Country of origin: France
Approvals: CE, UL, cUL, RoHS compliant
IP rating: IP20 (finger‑safe, no water protection)
3. Electrical Characteristics
Number of terminals: 40 (2 rows × 20)
Connection type: M3 screw terminals, captive screws
Conductor size: 0.2–2.5 mm² (24–14 AWG), single or stranded
Rated voltage: 300 VAC / 450 VDC
Rated current: 10 A per terminal (continuous)
Contact resistance: < 5 mΩ (initial)
Isolation: Galvanic isolation between adjacent terminals
Torque specification: 0.5–0.6 N·m (4.4–5.3 lb‑in)
4. Mechanical Specifications
Dimensions (H × W × D): 130 mm × 85 mm × 25 mm (5.12 in × 3.35 in × 0.98 in)
Mounting: Direct plug‑in to front of compatible Quantum I/O modules
Termination: Front‑facing screw terminals for easy access
Labeling: Pre‑numbered terminals (1–40)
Locking: Integrated snap‑lock (audible click when seated)
Removal: Tool‑free release tab
5. Environmental Ratings
Operating temperature: 0 °C to +60 °C, non‑condensing
Storage temperature: −25 °C to +85 °C
Humidity: 5 % to 95 % RH, non‑condensing
Maximum altitude: 2,000 m (6,562 ft) above sea level
Shock/vibration: Industrial grade (IEC 60068‑2‑6)
6. Compatibility
PLC series: Modicon Quantum
Compatible modules:
Analog input: 140ACI03000, 140ATI03000, 140AVI03000
Analog output: 140ACO02000, 140AVO02000, 140AMM09000
Discrete I/O: 140DAI, 140DAO, 140DDI, 140DDO series
Special function: 140ARI, 140DRA, 140DRC, 140EHC series
Not compatible with Quantum X80 or M340 series
7. Installation and Wiring
1. Preparation
Power off the target I/O module before installation or removal.
2. Attachment
Align the 140XTS00200 with the module’s front connector.
Push firmly until the snap‑lock engages (click).
3. Wiring
Strip wire to 6–7 mm (0.24–0.28 in).
Loosen screw, insert wire, tighten to 0.5–0.6 N·m.
Label wires per site standards.
4. Removal
Power off the I/O module.
Press release tab and pull straight out.
8. Maintenance
Inspection: Check terminal tightness and wire integrity quarterly.
Cleaning: Wipe with dry cloth; avoid solvents.
Torque check: Verify screw torque annually.
Storage: Keep dry and clean when unused.
9. Safety Instructions
Use only with compatible Modicon Quantum I/O modules.
Power off the I/O module during installation/removal.
Do not exceed rated voltage/current.
Maintain IP20 integrity; do not modify housing.
Indoor use only; avoid water and dust exposure.
10. Warranty
12‑month manufacturer warranty against defects in materials and workmanship.
Get a Quote