140XBP00400C
Description
140XBP00400C is a 4‑slot conformal coated backplane for Schneider Electric Modicon Quantum PLC. The C suffix stands for conformal coating, which protects the PCB against moisture, dust, chemicals, and corrosion — ideal for harsh industrial environments (chemical, water treatment, offshore, high humidity). It supports up to 4 Quantum modules (CPU, power, I/O, communication) and multi‑rack expansion via 140XBE series expanders.
2. Key Features
4 module slots: works with all standard Quantum CPU, I/O, comms, and bus modules
Conformal coated PCB: acrylic coating (UL 94 V‑0) for corrosion/humidity resistance
High‑speed 32‑bit backplane: 100 Mbps bandwidth, low latency
Integrated power distribution: +5 V logic, ±12 V I/O to each slot
Hot‑swap capable: insert/remove modules under power
Multi‑rack expansion: compatible with 140XBE10000 / 140XBE10000C
Robust construction: metal chassis, industrial vibration/noise immunity
Certifications: CE, UL, cUL; RoHS compliant
3. Technical Specifications
General
Model: 140XBP00400C
Type: 4‑slot conformal coated backplane
Slots: 4 (standard Quantum form factor)
Bus: 32‑bit high‑speed extension bus
Current draw: ~1400 mA (from rack PSU)
Power rails: +5 V (logic), ±12 V (I/O)
Weight: approx. 0.50 kg
Mounting: Quantum rack rails or panel‑mount kit
Environmental
Operating temperature: 0 °C to +60 °C
Storage temperature: −40 °C to +85 °C
Humidity: 10–95 % RH, non‑condensing
Altitude: ≤1,000 m (no derating)
Protection: IP20 (front); conformal coated (PCB)
Vibration: 10–150 Hz, 0.15 mm amplitude
Shock: 15 g, 11 ms half‑sine
Corrosion: salt mist & industrial gas resistant (coated)
Mechanical
Dimensions (W×H×D): 163 × 290 × 104 mm
Material: metal chassis, FR4 PCB with acrylic conformal coating
Connector: high‑density edge connector (module interface)
4. LED Indicators (on Modules, not Backplane)
PWR (Green): module power OK
RUN (Green): module active, backplane communication normal
FAULT (Red): module/backplane fault
LINK (Yellow): backplane data activity
5. Installation & Wiring
Rack Installation
Align 140XBP00400C with Quantum rack rails.
Slide in and secure with mounting screws (torque per specs).
Insert modules into slots 1–4 until latched.
Multi‑rack: connect backplane cables between 140XBP and 140XBE expanders.
Power & Grounding
Power: supplied by rack PSU; no direct user wiring
Ground: connect chassis to system earth ground
Cable routing: separate signal/power cables; shielded cables in high‑noise areas
6. Configuration (Unity Pro)
Open Unity Pro V7.0+.
In hardware config, add a 4‑slot rack and assign 140XBP00400C.
Insert I/O modules into slots 1–4.
Configure I/O addresses, diagnostics, fault handling.
Download to CPU; backplane initializes automatically.
7. Operation & Diagnostics
Normal Operation
All module PWR/RUN ON, FAULT OFF
Stable power + communication to 4 slots
Fault Conditions
Module FAULT ON: check seating, connector, or module failure
No PWR: verify rack PSU and backplane voltage rails
Comm errors: inspect cables, expanders, grounding
Diagnostic Data
Backplane voltage status (+5 V, ±12 V)
Module presence/absence flags
Bus communication quality metrics
8. Maintenance
Monthly: inspect seating, LEDs, cables
Quarterly: check screw torque; clean connectors (compressed air only)
Semi‑annually: verify ground continuity and shield integrity
Replacement: if connectors damaged or corrosion present
9. Safety & Compliance
Qualified personnel only for installation/wiring/maintenance
Disconnect all power before servicing
For industrial control systems only; not for direct life‑safety apps without safety layers
Follow local codes and EMC guidelines
10. Compatibility
Quantum CPUs: 140CPU65150, 140CPU67160, 140CPU68060, 140CPU69060+
Expanders: 140XBE10000, 140XBE10000C
I/O modules: all standard Quantum digital/analog, safety, specialty modules
Racks: compatible with Quantum 12/14/16‑slot systems
140XBP00400 vs 140XBP00400C
140XBP00400: standard (non‑coated), for clean/dry environments
140XBP00400C: conformal coated, for harsh/corrosive environments
Get a Quote