140NRP95400C
Description
1. Product Overview
140NRP95400C is a conformal-coated, dual‑channel multimode fiber optic repeater for Modicon Quantum RIO S908 remote I/O networks. It extends communication distance, provides electrical isolation, and supports redundant links for high availability in harsh environments.
Coated version: Improved resistance to dust, moisture, vibration, and corrosive atmospheres.
Form, fit, function identical to 140NRP95400 (non‑coated) except for conformal coating.
2. Key Features
Conformal coating: For harsh industrial environments.
Dual redundant fiber channels: 2×ST multimode ports + 1×BNC coaxial port.
Max distance: 3,000 m (62.5/125 µm) at 1 Mbps.
Optical isolation: Eliminates ground loops and EMI.
Hot‑swappable: Replace without system shutdown.
Diagnostic LEDs + relay: Real‑time status and fault alarming.
Certifications: CE, UL 508, CSA C22.2 No.142, FM Class 1 Div 2, RoHS compliant.
3. Technical Specifications
Electrical
Bus current: 700 mA @ 5 V DC
Power consumption: 5 W
Inrush current: 1 A @ 5 V DC
Optical (Multimode, 820 nm LED)
表格
| Fiber Type | Max Distance | Tx Power | Attenuation Range |
|---|---|---|---|
| 50/125 µm | 2,000 m | 3.5 dBm | −20 to −13 dB |
| 62.5/125 µm | 3,000 m | 3.5 dBm | −16 to −10 dB |
| 100/140 µm | 3,000 m | 5.0 dBm | −10.5 to −4 dB |
Receiver sensitivity: −30 dBm
Dynamic range: 20 dB
Detected silence: −36 dBm
Environmental
Operating temp: 0 °C to +60 °C
Storage temp: −40 °C to +85 °C
Humidity: 5–95 % (non‑condensing)
Altitude: Up to 2,000 m
Coating: Conformal acrylic coating (harsh environment protection)
Mechanical
Dimensions (W×H×D): 40.34 × 250 × 103.85 mm
Weight: 0.554 kg
Material: Polycarbonate (PC) + conformal coating
4. LED Indicators & Diagnostic Relay
LED Status
表格
| LED | Color | State | Meaning |
|---|---|---|---|
| READY | Green | Off | No power / internal fault |
| On | Powered & operational | ||
| COM ACT | Green | Off | No coaxial activity |
| Flashing | Coaxial data transfer | ||
| OPT FAULT | Red | Off | Optical link OK |
| On | Optical link failure | ||
| ERR | Red | Off | Module healthy |
| On | Internal fault / config error |
Diagnostic Relay
Normal: Energized (contacts closed)
Fault: De‑energized (contacts open) – triggers on power loss, module failure, or optical fault
5. Installation
5.1 Rack Mounting
Ensure Quantum rack power is OFF (or hot‑swap in powered rack).
Align module with rack slots, insert firmly until seated.
Secure with rack latch.
5.2 Cable Connections
Fiber Ports (ST)
Tx → Rx of remote module; Rx → Tx of remote module.
Cable: Multimode (50/125, 62.5/125, 100/140 µm).
Min bend radius: 10× cable diameter.
Coaxial Port (BNC)
Cable: 75 Ω (RG‑6 or equivalent).
Max length: 100 m (copper segment).
5.3 Harsh Environment Notes
The conformal coating protects against condensation, dust, and mild corrosives, but do not expose to direct liquid spray or immersion.
6. Configuration
No manual configuration required: Module auto‑detects RIO S908 network.
Software: Unity Pro V7.0 or later; add to I/O list, download project.
Topologies: Point‑to‑point, dual redundant, multidrop (up to 31 drops).
7. Operation & Maintenance
Normal Operation
READY: Green ON
COM ACT: Green flashing
OPT FAULT: Red OFF
ERR: Red OFF
Troubleshooting
OPT FAULT ON:
Check Tx/Rx reversal, dirty/damaged connectors, tight bends, or wrong fiber type.
ERR ON:
Re‑seat module, check 5 V backplane power, replace module if fault persists.
READY OFF:
Verify rack power, check backplane short circuits.
Maintenance
Quarterly: Inspect and clean ST connectors (isopropyl alcohol).
Semi‑annually: Test diagnostic relay.
Firmware: Update via Unity Pro (check Schneider Electric website).
8. Safety
Qualified personnel only for installation/service.
Disconnect power before rack maintenance.
Laser safety: Class 1 LED (820 nm) – no eye hazard under normal use.
9. Ordering & Compatibility
140NRP95400C: Coated multimode, ST connectors.
140NRP95400: Non‑coated version.
140NRP95401C: Single‑mode alternative (LC duplex).
10. Support
Manufacturer: Schneider Electric
Documentation: S1A84131.02 (PDF)
Website: www.schneider‑electric.com
Get a Quote