140NRP31200C
Description
1. General Description
2. Product Overview
Model: 140NRP31200C (Multi-mode, MM, Conformal-coated)
Function: 2‑channel 100 Mb/s Ethernet ↔ multi-mode fiber conversion
Fiber: Multi‑mode (50/125 µm, 62.5/125 µm), LC connectors
Copper: 2×RJ45, 10/100 Mb/s auto‑negotiation
Protocol: Quantum RIO, Modbus TCP, Ethernet/IP (via adapter)
Redundancy: Supports fiber link redundancy and RSTP
Coating: Conformal coated for protection against dust, moisture, and corrosion
3. Technical Specifications
Electrical
Backplane voltage: 5 V DC
Current consumption: 1000 mA (max)
Power dissipation: 5 W (max)
Inrush current: 1 A (5 V DC)
Optical (Multi‑mode, 1310 nm)
Tx wavelength: 1310 nm
Rx sensitivity: −30 dBm
Detect silence: −45 dBm
Attenuation range:
50/125 µm: −23.5 to −14 dBm
62.5/125 µm: −20 to −14 dBm
Max distance:
50/125 µm: 2000 m
62.5/125 µm: 3000 m
Environmental
Operating temperature: 0 °C to +60 °C
Storage temperature: −40 °C to +85 °C
Humidity: 0–95% RH, non‑condensing
Altitude: Up to 2000 m
Protection: Conformal coated (improved resistance to dust, moisture, corrosive gases)
Standards: CE, UL 508, CSA C22.2 No.142, FM Class 1 Div 2, RoHS
Physical
Dimensions: Standard Quantum module (250 mm × 103.85 mm × 40.34 mm)
Mounting: Quantum rack slot, hot‑swap capable
Connectors: 2×LC (fiber), 2×RJ45 (copper)
Weight: Approx. 0.5 kg
4. LED Indicators
RDY (Green): Solid = Module operational; Blinking = Initialization/self‑test
ERR (Red): Solid = Hardware/config fault; Blinking = Minor alarm
STS1/FX1 ACT (Green): Channel 1 link/activity
STS2/FX2 ACT (Green): Channel 2 link/activity
5. Installation
ESD protection: Wear anti‑static wristband before handling.
Power off: Disconnect rack power before insertion/removal.
Insert module: Align with empty Quantum slot, push firmly, tighten screw.
Connect cables:
Fiber: LC connectors (Tx ↔ Rx between devices)
Copper: RJ45 to switch/PLC/IO
Cable management: Avoid sharp bends; secure cables to prevent tension.
Power on: Restore power; verify RDY LED solid green.
6. Configuration
Software
Compatible with EcoStruxure Control Expert 14.0+ (Unity Pro)
No programming required for basic conversion; set network parameters in hardware config.
Network Settings
Set IP, subnet mask, gateway for copper ports (if using Modbus TCP).
Enable RIO fiber link in Quantum CPU configuration.
Configure redundancy (RSTP) if required.
7. Operation
Normal: RDY solid green; ACT LEDs blink on data transfer.
Fiber link: Tx/Rx must be crossed between two modules.
Redundancy: Automatically switches to backup fiber link on primary failure.
Hot swap: Replace module without stopping the system (same model).
8. Maintenance & Troubleshooting
Routine Maintenance
Inspect cables/connectors monthly; clean fiber ends with lint‑free cloth.
Check LED status; update firmware via Control Expert if needed.
Conformal coating reduces cleaning frequency; avoid harsh chemicals.
Common Issues
RDY off: Backplane power fault or poor contact → Reseat module, check power.
ERR solid: Config mismatch or hardware damage → Verify config, replace module.
No fiber link: Tx/Rx reversed, dirty connectors, or cable break → Check polarity, clean, replace cable.
Copper port no link: Cable fault or speed mismatch → Replace cable, check auto‑negotiation.
9. Safety & Compliance
Install/maintain only by qualified personnel.
Disconnect power before servicing.
Use only approved fiber/copper cables.
Comply with local EMC and safety regulations.
10. Ordering Information
140NRP31200C: Multi‑mode fiber converter (2×LC, 2×RJ45, 100 Mb/s, conformal coated)
140NRP31200: Non‑coated multi‑mode version (reference only)
140NRP31201C: Conformal coated single‑mode version (reference only)
Get a Quote