140EHC10500C
Description
1. General Information
Model: 140EHC10500C
Brand: Schneider Electric
Series: Modicon Quantum
Type: High‑speed counter module (5 channels, 8DI/8DO)
Purpose: High‑speed pulse counting, position tracking, frequency/period measurement, event sequencing for Quantum PLC systems.
2. Specifications
2.1 Counter Channels
Quantity: 5 independent channels
Resolution: 32‑bit signed
Max Input Frequency:
100 kHz (5 VDC differential encoder)
20 kHz (24 VDC single‑ended encoder)
Input Types: A/B quadrature, pulse/direction, up/down, event
Modes: Event counter, differential (quadrature) counter, period/frequency meter, watchdog (pulse presence).
2.2 Digital Inputs (8 points)
Voltage: 24 VDC nominal
Type: Sink (NPN), 7 mA typical
Isolation: 2500 V AC (channel‑to‑backplane)
Response Time: ≤1 µs
2.3 Digital Outputs (8 points)
Voltage: 24 VDC nominal
Type: Sourcing transistor (PNP)
Current: 0.5 A per channel (max)
Protection: Short‑circuit & overload
Isolation: 2500 V AC
2.4 Power & Environment
Backplane Power: 5 VDC
Power Dissipation: ≤6 W
Operating Temperature: 0 °C to +60 °C
Storage Temperature: −40 °C to +85 °C
Relative Humidity: 5%–95% (non‑condensing)
Certifications: CE, UL, CSA, RoHS
2.5 Mechanical
Form Factor: Single slot, Quantum rack
Dimensions (W×H×D): 104 × 40 × 250 mm
Weight: ~0.3 kg
Connector: 40‑pin terminal block (ordered separately)
3. Operation Modes (per channel)
Event Counter: Counts rising/falling edges; 32‑bit wrap‑around.
Differential (Quadrature) Counter: A/B phase decoding (×1/×2/×4); auto direction.
Period/Frequency Meter: Measures µs period or Hz frequency; configurable gate time.
Watchdog Timer: Triggers output if no pulse within preset time (safety).
4. LED Indicators
PWR: Green = power OK
RUN: Green = module active
ERR: Red = fault (config/wiring/overload)
CH1–CH5: Green = counting activity
5. Installation
Power off the Quantum rack.
Insert module into any empty slot; push firmly until seated.
Secure front panel screws.
Wire encoders/sensors to the 40‑pin terminal block (use shielded cable).
Power on; confirm PWR and RUN LEDs are green.
6. Configuration (EcoStruxure Control Expert / Unity Pro)
Add 140EHC10500C to hardware configuration.
Configure each channel:
Select mode (event/differential/period/watchdog)
Set input type (5 V/24 V, single‑ended/differential)
Define presets, setpoints, and output mapping
Assign 8 DI / 8 DO to I/O addresses.
Download configuration; check ERR LED.
7. I/O Mapping
Inputs 0–7: 24 VDC sink; read via Quantum input table.
Outputs 0–7: 24 VDC sourcing; write via Quantum output table.
Counter Data: 32‑bit values in PLC memory (current count, preset, status per channel).
8. Applications
High‑speed pulse counting (encoders, flow meters, tachometers)
Position/speed monitoring (conveyors, machine tools, packaging)
Frequency/period measurement
Event logging & sequencing
Safety pulse monitoring (watchdog)
9. Troubleshooting
PWR Off: Check backplane power; re‑seat module.
RUN Off: Verify CPU is in RUN; re‑download config.
ERR On: Check wiring, encoder voltage, config errors, or output overload.
No Counting: Verify encoder power, A/B phase wiring, and input frequency limits.
10. Reference Documents
Official Manual: Quantum 140EHC10500 User Manual (EcoStruxure Control Expert)
Doc No.: 33002491K01000 (Rev 09, Dec 2018)
Software: EcoStruxure Control Expert (Unity Pro) v7.0+