51309140175
Description
Product Overview
General Information
Part Number: 51309140‑175
Alternate PN: MC‑TSTX03
Type: Smart Transmitter Interface FTA (STI FTA)
Compatible IOPs: MU‑PSTX03 (51304756‑100), MC‑PSTX03 (51304756‑150)
Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)
Status: Discontinued (EOL); refurbished/used available
Origin: United States
Certification: CE compliant
Coating: Conformal coated (for harsh environments)
Terminals: Orange compression screw terminals
Dimensions: 307 mm (12 in, Size B) × 100 mm × 35 mm
Weight: Approx. 0.5–0.6 kg
Redundancy: Supports redundant IOP configurations
Technical Specifications
Input Channels: 16 single‑ended, isolated inputs
Signal Range: 4–20 mA DC analog with HART® digital overlay
Protocol: HART® Revision 5/7 compatible
Termination: Orange compression screw terminals (field wiring)
Connector: 50‑pin ribbon connector (to PSTX IOP)
Isolation: 500 VAC channel‑to‑ground; 1500 VAC field‑to‑system
Power: 24 VDC (15–30 VDC), ≤4 W
Operating Temperature: 0°C to +55°C (32°F to 131°F)
Storage Temperature: -40°C to +85°C (-40°F to 185°F)
Humidity: 10%–90% RH, non‑condensing
Key Features
Size B (12 in) Form Factor: Fits standard UCN I/O chassis Size B slots.
Orange Screw Terminals: High‑visibility orange terminals for easy HART transmitter wiring ID.
Conformal Coating: Protects against moisture, dust, and chemicals for harsh industrial environments.
HART® Communication: Enables digital data (diagnostics, configuration) from smart transmitters.
Isolated Channels: Galvanic isolation reduces noise and ground loops.
Redundancy Support: Works with standard and redundant MU‑PSTX03 / MC‑PSTX03 IOPs.
Applications
Process Industries: Chemical, petrochemical, power, oil & gas, pulp & paper.
System Role: Field termination & HART signal conditioning for smart transmitters in Honeywell DCS.
Typical Uses:
Connecting HART‑enabled pressure, flow, level, temperature transmitters.
Transmitting 4–20 mA analog + HART digital to PSTX IOPs.
Remote configuration and diagnostics of smart field devices in humid/dusty/chemically exposed areas.
Installation & Wiring
ESD Protection: Use anti‑static wristbands and ESD‑safe surfaces.
Power Off: De‑energize chassis before insertion/removal.
Chassis Installation:
Insert FTA into Size B slot in UCN I/O chassis.
Secure with mounting screws.
Connect 50‑pin ribbon cable to PSTX IOP.
Field Wiring:
Use shielded twisted‑pair (STP) cable for HART signals.
Connect transmitter ± to designated orange terminals.
Ground shields at one end only to avoid ground loops.
Configuration: Enable HART communication via Experion PKS/TPS software.
Maintenance
Inspection: Check orange terminal tightness, cable connections, 24 VDC power.
Cleaning: Use dry, soft cloth; avoid liquid cleaners.
Troubleshooting:
Verify wiring polarity and shield grounding.
Check for short circuits or ground faults.
Use HART diagnostics to isolate transmitter/channel issues.
Safety Notes
Disconnect chassis power before installation/maintenance.
Operate within rated temperature/humidity limits.
Do not modify or disassemble (voids warranty).
Comply with site ESD and safety procedures.
Related Model Comparison
| Feature | 51309140‑175 (MC‑TSTX03) | 51309140‑125 (MU‑TSTX03) |
|---|---|---|
| Form Factor | Size B (12 in) | Size B (12 in) |
| Coating | Conformal | Non‑conformal |
| Terminals | Orange screw | Orange screw |
| Redundancy | Supported | Supported |
| Part Suffix | ‑175 | ‑125 |