51309138275
Description
Product Overview
General Information
Part Number: 51309138‑275
Alternate PN: MC‑TAIH53
Type: High‑Level Analog Input FTA (HLAI FTA)
Compatible IOPs: MU‑PAIH03 (51304754‑100), MC‑PAIH03 (51304754‑150)
Compatible Systems: Honeywell TDC3000, TPS, Experion PKS (UCN)
Status: Discontinued (EOL); refurbished/used available
Origin: United States
Certification: CE compliant
Coating: Conformal coated (harsh environment protection)
Terminals: Red compression screw terminals
Dimensions: 307 mm (12 in, Size B) × 100 mm × 35 mm
Weight: Approx. 0.5–0.6 kg
Redundancy: Supports redundant IOPs
Technical Specifications
Input Channels: 16 single‑ended high‑level analog inputs
Signal Ranges: 0–10 VDC, ±5 VDC, ±10 VDC
Termination: Red compression screw terminals (field wiring)
Connector: 50‑pin ribbon connector (to IOP)
Isolation: 500 VAC channel‑to‑ground
Power: 24 VDC (15–30 VDC), ≤3 W
Operating Temperature: 0°C to +55°C (32°F to 131°F)
Storage Temperature: -40°C to +85°C (-40°F to 185°F)
Humidity: 10%–90% RH, non‑condensing
Key Features
Size B (12 in) Form Factor: Fits standard UCN I/O chassis Size B slots.
Red Screw Terminals: High‑visibility red compression screws for easy wiring ID and maintenance.
Conformal Coating: Protects against moisture, dust, and chemicals for harsh industrial environments.
Redundancy Support: Works with standard and redundant MU‑PAIH03 / MC‑PAIH03 IOPs.
CE Compliance: Meets EU EMC directives.
16‑Channel Density: High‑density voltage input termination, saving cabinet space.
Applications
Process Industries: Chemical, petrochemical, power generation, oil & gas, pulp & paper.
System Role: Field termination & signal conditioning for high‑level analog inputs in Honeywell DCS.
Typical Uses:
Connecting voltage‑output pressure, flow, level, and temperature transmitters.
Isolating and routing analog signals to HLAI IOPs.
High‑precision data acquisition in humid/dusty/chemically exposed areas.
Installation & Wiring
ESD Protection: Use anti‑static wristbands and ESD‑safe surfaces.
Power Off: De‑energize the I/O chassis before insertion/removal.
Chassis Installation:
Insert FTA into Size B slot in UCN I/O chassis.
Secure with mounting screws.
Connect 50‑pin ribbon cable to mating IOP.
Field Wiring:
Use shielded twisted‑pair cable for voltage signals.
Connect signal positive/negative to designated red compression terminals.
Ground shields at one end to avoid ground loops.
Configuration: Set channel ranges (0–10 V, ±10 V, etc.) via Experion PKS/TPS software.
Maintenance
Inspection: Check red terminal tightness, cable connections, and 24 VDC power.
Cleaning: Use dry, soft cloth; avoid liquid cleaners.
Troubleshooting:
Verify wiring polarity and integrity.
Check for short circuits or ground faults.
Use system diagnostics to isolate faulty channels.
Safety Notes
Disconnect chassis power before installation/maintenance.
Operate within rated temperature/humidity limits.
Do not modify or disassemble (voids warranty).
Comply with site ESD and safety procedures.
Comparison with Related Models
| Feature | 51309138‑275 (MC‑TAIH53) | 51309138‑225 (MU‑TAIH53) | 51309138‑175 (MC‑TAIH13) | 51309138‑125 (MU‑TAIH13) |
|---|---|---|---|---|
| Form Factor | Size B (12 in) | Size B (12 in) | Size B (12 in) | Size B (12 in) |
| Coating | Conformal | Non‑conformal | Conformal | Non‑conformal |
| Terminals | Red screw | Red screw | Black screw | Black screw |
| Redundancy | Supported | Supported | Supported | Supported |
| Part Suffix | ‑275 | ‑225 | ‑175 | ‑125 |
Get a Quote