330930-060-01-05
Description
I. Model Breakdown
330930: 3300 XL NSv Series Extension Cable
060: Length 6.0 m
01: Stainless steel armor + FEP outer sheath (oil-resistant, wear-resistant, high-temperature resistant)
05: Explosion-proof certification (ATEX/IECEx/CSA), suitable for hazardous areas
II. Core Parameters
1. Mechanical Structure
Length: 6.0 m
Structure: Inner insulation → Shielding → Stainless steel armor → FEP outer sheath
Joints: Both ends ClickLoc® coaxial quick connectors, waterproof and dustproof
Minimum bending radius: ≥ 25 mm
Weight: Approximately 0.9 kg
2. Electrical Characteristics
Compatible System: 3300 XL NSv Eddy Current Sensor
Impedance: 50 Ω
Frequency Response: 0–10 kHz
Transmission: Low loss, anti-interference, suitable for long-distance signal transmission
3. Environment and Explosion-proof
Operating Temperature: -40°C ~ +125°C
Protection Grade: IP67
Explosion-proof: ATEX/IECEx/CSA Certification (05), suitable for flammable and explosive hazardous areas
Anti-vibration: 10 g (10–1000 Hz)
III. System Compatibility (Must be Matched as a Set)
Probe: 330901-00-00 (1.0 m internal cable, NSv standard probe)
Preamplifier: 330980-50-00 / 330980-70-00 (Total length = Probe length + Cable length)
Example: 1.0 m + 6.0 m = 7.0 m (Order length of the preamplifier)
Monitoring Rack: 3300 TSI, 3500 TSI
Monitoring Module: 3500/40M (Vibration), 3500/50M (Phase / Speed)
IV. Key Models of the Same Specification (6.0m) Comparison Table
Model Length Armor + FEP Explosion-proof Certification Applicable Scenarios
330930-060-01-05 6.0m ✅ ✅ Explosion-proof / Hazardous Areas (Oil/Gas / Chemicals)
330930-060-01-00 6.0m ✅ ❌ General Industry, Wear-resistant Scenarios
330930-060-00-05 6.0m ❌ ✅ Danger Zones, Ordinary Sheaths
V. Installation Points
Length Matching: Probe Length + Extension Cable Length = Nominal Length of the Preamplifier, otherwise the measurement will be non-linear and inaccurate.
Joint Protection: Avoid oil and dust, use protective caps when not in use.
Cable Routing Fixation: Fix every 0.5–1m, keep away from high-temperature/high-pressure pipes, avoid hard bending.
Grounding Specifications: Shielding Layer is only single-ended grounded on the preamplifier side, to prevent circulating interference.
Get a Quote