330980-71-00
Description
I. Model Positioning
330980: High-temperature-specific phase and speed probe, not compatible with conventional vibration probes
71: Side-out narrow-body structure, suitable for narrow installation spaces
00: The body does not come with a built-in cable, and it needs to be used in conjunction with an extension cable
Usage: For the high-temperature shell areas of steam turbines and gas turbines, only for phase picking and speed monitoring, not applicable for shaft vibration and displacement measurement
II. Core Parameters
1. Mechanical Structure
Probe Type: Electric Eddy Current High-Temperature Phase and Speed Special Probe
Installation Thread: 3/8-24 UNF standard thread
Outgoing Line Form: Side-out narrow-body design
Cable Configuration: No built-in cable, use 330130 series extension cable
Shell Material: High-temperature-resistant stainless steel material
Protection Grade: IP67, dustproof, moisture-proof, and oil-resistant
2. Electrical Characteristics
Measurement Principle: Non-contact Eddy Current Induction
Adapter Compatibility: 330180 standard model, 330181 high-temperature model
Sensitivity: 7.87V/mm
Frequency Response: 0~10kHz, full coverage of the unit's speed range
Pulse Characteristics: Signal edge regular, no lost pulses, no noise
Power Supply: -24VDC ±10%
3. Environmental Tolerance
Probe Working Temperature: -40℃~+175℃
Cable Adaptation Temperature: -40℃~+125℃
Anti-Vibration Grade: 10g (10~1000Hz)
Low temperature drift coefficient, stable signal in high-temperature conditions without deviation
4. System Adaptation
Adaptable Rack: 3300 TSI, 3500 TSI system
Adaptable Module: 3500/50E, 3500/50M Speed Phase Module
Matching Cable: 330130 series 5m / 9m extension cable
III. Installation Tips
1. Installation Gap
Standard installation gap: 1.0~1.5mm
Preferred material for the measured object: 4140 steel, the detection surface area is more than three times the diameter of the probe
Leave 5mm or more clearance around the probe to avoid metal interference
2. Wiring Standards
Three-wire wiring, the core wire is the signal end, the inner shield is the common end, and the outer shield is the grounding end
Shielded wire is only grounded on one side of the preamplifier to eliminate circulating interference
3. Installation Steps
Clean the installation hole and impurities on the measured surface
Insert the probe contact end face and retract 1.25mm as the standard spacing
Lock the anti-loosening nut, and the tightening torque is controlled at 8~10N・m
Straighten the wiring, the bending radius of the cable is not less than 25mm
IV. Common Faults
No pulse output: Check the installation gap, power supply line, wiring terminals, and cable continuity
Signal fluctuation and noise: Check the grounding method, whether the cable is close to strong electrical equipment
High-temperature signal abnormality: Confirm the probe working temperature, installation tightness, and detection spacing
V. Comparison of the Same Model
330980-71-00: No built-in cable, select the extension cable as needed
330980-71-05: Comes with 5m built-in cable, can be directly connected to the preamplifier on site
The structural temperature tolerance, electrical parameters, and adapter accessories are completely the same as the above two models