330-980-71-05
May 22, 2026

330-980-71-05

Core Parameters (330980-X0-00) 1. Mechanical Structure Probe Type: Electromagnetic Eddy Current, Special for High Temperature Phase Detection Installation Thread: Standard Industrial Thread (fits original holes of gas turbines / steam turbines) Cable Type: No Built-in Cable, must be equipped with 330130 Series Extension Cable Shell Material: High Temperature Stainless Steel (resistant to 175℃, vibration resistance 10g) Protection Grade: IP67 (dustproof, oilproof, moistureproof) 2. Electrical Characteristics Measurement Principle: High Frequency Eddy Current (Non-contact) Adapter Compatibility: 330180 (standard), 330181 (high temperature) Sensitivity: 7.87 V/mm (200 mV/mil) Frequency Response: 0~10 kHz (covers 1~99999 rpm) Trigger Pulse: Steep edge, no lost pulse, no noise (high phase accuracy) 3. Environmental Tolerance (Critical) Probe Temperature: –40℃ ~ +175℃ (High Temperature Grade) Extension Cable Temperature: –40℃ ~ +125℃ Vibration Resistance: 10 g (10~1000 Hz) Temperature Drift: Extremely Low (Signal Stable at High Temperature) 4. System Compatibility Compatible Rack: 3500 TSI, 3300 TSI Compatible Module: 3500/50E, 3500/50M (Speed / Phase Detection) Extension Cable: 330130-050-01 (5m), 330130-090-01 (9m) III. Installation Guide (Key Points) 1. Installation Gap (Critical!) Recommended Gap: 1.0~1.5 mm (top of phase detection teeth / groove) Target Surface: 4140 Steel (standard), Area ≥ 3 times the probe diameter Side / Back Clearance: ≥ 5 mm (avoid metal interference) 2. Wiring (Three-Wire System, Adapter → Probe) Core Wire: Signal (+) Inner Shield: Common (–) Outer Shield: Ground (Single-ended Ground, Grounded on Adapter Side) Total Cable Length: Probe + Extension Cable = 5m/9m, cannot be cut随意 3. Installation Steps Clean Installation Holes and Measured Surface (No Oil Stains, No Bumps) Manual Insert the Probe to a Slight Contact, then Retract 1.25 mm Lock the Anti-Slip Nut (Torque 8~10 N·m) Fix the Cable (Avoid Twisting, Bend Radius ≥ 25 mm) Adapter Installed on Insulation Board (Floating, Avoid Ground Current) IV. Calibration and Debugging Power Supply: Adapter -24 VDC ±10% Gap Voltage: –10.0 ±0.5 VDC (Static, No Speed) Speed Module Configuration: Sensor Type: 3300 XL NSv Sensitivity: 7.87 V/mm Pulse per Revolution: 1~255 (Number of Phase Detection Teeth) V. Common Faults and Troubleshooting No Pulse Signal: Check Gap (too large / too small), Wiring, Adapter Power Supply, Cable Break Signal Jumping / Noise: Poor Grounding, Double-ended Grounding of Outer Shield, Cable Close to Strong Electricity High Temperature Drift: Too Small Gap, Probe Over 175℃, Extension Cable Over Temperature Lost Pulse: Phase Detection Tooth Deformation, Installation Loose, Excessive Vibration VI. Supplementary List Probe: 330980-X0-00 (No Built-in Cable) Extension Cable: 330130-050-01 (5m) or 330130-090-01 (9m) Adapter: 330180 (Standard) / 330181 (High Temperature) Monitoring Module: 3500/50E (Recommended) / 3500/50M VII. Difference from Ordinary Probes Purpose: 330980 = Phase Detection / Speed; 330104 = Shaft Vibration / Displacement Temperature resistance: 330980 = 175℃; 330980 - 71 - 05 (Bently Nevada high-temperature phase probe with built-in cable) Model: 330980 - 71 - 05 (often written as 330-980-71-05) Brand: Bently Nevada (Baker Hughes) Series: 3300 XL NSv high-temperature phase / speed sensor system Function: High-temperature built-in-cable phase probe for combustion engines / steam turbines (–40℃ to +175℃), providing phase reference, speed, zero speed, reverse, overspeed pulse signals, compatible with 3500/50E, 3500/50M speed modules. Normal = 125℃ Signal: 330980 focuses on pulse integrity; normal focuses on linear range Operating conditions: 330980 must be used in the high-temperature section of combustion engines and cannot be replaced.

Description

I. Model Positioning

330980: High-temperature dedicated phase / speed probe (not ordinary shaft vibration probe)

71: Structural Configuration = With Built-in Cable + Side-Out Type (NSv)

05: Built-in Cable Length 5 meters

Usage: Gas turbine, steam turbine high-temperature casing / exhaust end, only for phase detection + speed measurement, not for shaft vibration / displacement.

II. Core Parameters (330980-71-05)

1. Mechanical Structure

Probe Type: Electromagnetic Vibration, High-Temperature Phase Detection Specialized

Installation Thread: 3/8 - 24 UNF (Standard)

Cable Type: Built-in 5-meter cable, no need to add extension cable

Shell Material: High-temperature resistant stainless steel (resistant to 175°C, vibration resistance 10g)

Protection Grade: IP67 (dustproof, oilproof, waterproof)

Outgoing Line Method: Side-Out (NSv, narrow type)

2. Electrical Characteristics

Measurement Principle: High-frequency Electromagnetic Vibration (Non-contact)

Adapter Compatibility: 330180 (Standard), 330181 (High Temperature)

Sensitivity: 7.87 V/mm (200 mV/mil)

Frequency Response: 0 - 10 kHz (covers 1 - 99999 rpm)

Trigger Pulse: Steep edge, no lost pulse, no noise (high phase accuracy)

Input Voltage: –24 VDC (±10%)

3. Environmental Tolerance (Key)

Probe Temperature: –40°C ~ +175°C (High Temperature Grade)

Cable Temperature: –40°C ~ +125°C

Vibration Resistance: 10 g (10 - 1000 Hz)

Temperature Drift: <0.5%/°C (Signal Stable at High Temperature)

4. System Adaptation

Adaptable Rack: 3500 TSI, 3300 TSI

Adaptable Module: 3500/50E, 3500/50M (Speed / Phase)

Total Cable Length: Built-in 5 meters, cannot be cut

III. Installation Tips (Consistent with 330980-X0-00)

1. Installation Gap

Recommended Gap: 1.0 - 1.5 mm (Phase Detection Tooth Top / Groove)

Target Surface: 4140 Steel, Area ≥ 3 times the probe diameter

Side / Back Clearance: ≥ 5 mm (Prevent Metal Interference)

2. Wiring (Three-wire System, Adapter → Probe)

Core Wire: Signal (+)

Inner Shield: Common (–)

Outer Shield: Ground (Single-ended Ground, Ground on Adapter Side)

3. Installation Steps

Clean Installation Holes and Measured Surface (No Oil Stain, No Bumps)

Manual Insert the Probe to a Slight Contact, Then Retreat 1.25 mm

Lock the Anti-Slip Nut (Torque 8 - 10 N·m)

Fix the Cable (Avoid Twisting, Bend Radius ≥ 25 mm)

IV. Differences from 330980-X0-00

71-05: With 5-meter Built-in Cable, Directly Connect to Adapter on Site

X0-00: No Built-in Cable, Must be Paired with 330130 Extension Cable

Other Parameters (Temperature Resistance, Sensitivity, Adaptable Module) Are Exactly the Same

V. Complementary List

Probe: 330980-71-05 (Built-in 5-meter Cable)

Adapter: 330180 (Standard) / 330181 (High Temperature)

Monitoring Module: 3500/50E (Recommended) / 3500/50M


Get a Quote