3500/42
Description
I. Model Description (Common Format)
3500/42M: Standard type, most commonly used
3500/42-02-R0: With internal terminals, universal type
3500/42-04-00: 4 × displacement / acceleration channels
Part Number Examples: 176449-02 (front panel), 128229-01 (back panel)
II. Core Functions
4 independent channels: Each channel is programmable, supporting eddy current (displacement), speed, and acceleration sensors.
Monitoring Parameters:
Radial vibration (peak-to-peak, 1X/2X, band-pass)
Axial displacement / thrust position, differential expansion, eccentricity
Casing vibration (velocity / acceleration)
Over-speed, reverse rotation, zero speed (combined with phase)
Alarm Logic: Each channel has three levels of high / high-high / dangerous, supports triple-out-two interlock, complies with API 670.
III. Key Parameters (3500/42M)
Sensor Compatibility: 3300XL eddy current, 190501 speed, IEPE acceleration
Frequency Range: 0.5Hz - 10kHz
Measurement Accuracy: ±2% of full scale
Resolution: 0.1μm (displacement)
Power Supply: –24VDC, power consumption ≈ 7W
Temperature: –20℃ - +65℃
Hot Swap: Supported
Size: Full-height module (same as 3500/40M)
IV. 3500/42 (42M) vs 3500/42E (Enhanced) Table
Comparison item 3500/42 (42M, standard) 3500/42E (Encore, enhanced)
Hardware platform Classic New generation Encore
Accuracy ±2% FS ±1% FS
Temperature range –20 to +65℃ –40 to +70℃
Anti-interference Standard EMI filtering Enhanced EMI filtering
Diagnostic capability Basic alarm Sensor break / short circuit / drift self-check
Channel configuration Partially fixed 4 channels fully programmable
Status Out of production / reduced quantity Preferred for main projects, especially for new projects
V. Typical applications and accessories
Equipment: Steam turbines, compressors, fans, pumps, generators
Industry: Power, petrochemical, metallurgy, oil and gas
Accessories:
Probe: 330104/05/08 (electro-vibration)
Extension cable: 330130 (5m/9m)
Frame: 3500/22 (power / interface), 3500/50E (phase alignment)
VI. Selection suggestions
New projects: Directly select 3500/42E, with stronger accuracy, stability and diagnostic capabilities
Old project spare parts: Can purchase 3500/42M (some models still in stock)
Channel requirement: 4 channels → 42M/42E; 2 channels → 3500/40M
Get a Quote